4 Wiring

Before selecting the wiring, consider the following factors:

• Current carrying capacity of the wire

• Maximum wire length needed

• Maximum ambient temperature.

IMPORTANT
Use the table below as a guide only. Ensure that the installation complies with the specific wiring
rules applicable to your country or area of jurisdiction.


Shelf number of
2 x 1000VA inverters
cascaded

Input current
maximum @40Vdc

AC output

Minimum size of DC
input wire

AC output

1 46A

#8

AWG

2 92A

#4

AWG

3

4

5

6

Shelf number of
2 x 1500VA inverters
cascaded

Input current
maximum @40Vdc

Minimum size of DC
input wire

1 69A

#6

AWG

2 137.9A

#2

AWG

3

4

5

6

100A

#2 AWG

Table D–Wiring guide

NOTE: DC input to maximum two shelves.


CN11: Parallel
signal port
with inverter

CN6/CN7:
DC Power of
Controller

CN3: Alarm
output of
STS

CN2, CN6:
RS485
Port

CN13:
RS232 Port

CN7~CN11:
Relay
Contacts

CN4: Reserved
for “battery
control”

CN3: CAN COM port
other controller
module

INV.
Line

INV.
Ground

INV.
Neutral

AC Output L

AC Ground

AC Input L

AC input/output N

Figure 9–Rear view of STS chassis showing connections