Illustration of operation, Sts operating principles, 3 illustration of operation – Alpha Technologies INEX 100A STS Module and MBS+PDU User Manual

Page 12: 4 sts operating principles

Advertising
background image

Argus Technologies Ltd.

019-061-C0 Rev A WC

Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved.

Page 2 of 26

1.3

Illustration of Operation

STS-100 is designed to avoid operational disruptions of critical loads. This automatic static transfer switch (STS)
automatically transfers critical loads from the primary AC power source to an alternative AC power source in the
event of interruption or abnormal conditions.

Figure 2–STS-100 operation illustrated

STS-100 transfers the critical load between power sources in less than 1/4 cycle upon loss of source. The fast
transfer enables further redundancy in distribution, adding level of availability, flexibility and reliability to our
customer’s power infrastructure.

1.4

STS Operating Principles

MBS Status

Schematic operating principle of STS

Description

Mains

Bypass

(P1)

Mains

Inverter

Load

Backfeed Relay

Bypass Relay

MBS Main Contact1

MBS Main Contact2

SCR1

SCR2

Mains Bypass:

Load is powered through the
MBS by Mains AC

STS can be removed from the
system

MBS can only be switched
from P1 to P2 position

SCR2 open, SCR1 and Back-

feed Relay closed

Alternative AC Source
(UPS, generator, utility)

Inverter Output Voltage

STS Module

Sine Wave Output

Load

Communication Line

Power Line