Mechanical

STS Module:

Dimensions: 88mm H x 218mm W x 270mm D

[3.5" H x 8.6" W x 10.6" D]

Weight:

2.1 kg (4.6 lb.)


STS Shelf:

Dimensions: 88.1mm H x 483mm W x 330mm D

[3.5" H x 19" W x 13" D]

Weight:

7.0 kg (15.4 lb.)


Hot Swappable:

STS hot swappable only available when MBS at Mains Bypass and
Inverter Bypass position


Mechanical Bypass Switch Requirement: The STS module used with a Mechanical Bypass Switch module shall

provide voltage free system maintenance. It should be interlocked with
the static switch module so that the static switch module cannot be
removed without the maintenance bypass being activated.


Force Cooling:

Two fans


Alarm Relay:

Dry contact alarm output


Environmental

Operating Temperature:

-20 to +70°C (-4 to +158°F)
-20 to +50°C (-4 to +122°F) with full performance


Storage Temperature:

-30 to +85°C (-22 to +185°F)


Operating Humidity:

0 to 95% relative, non-condensing


Heat Dissipation:

Forced air cooling


Operating Altitude:

1500m (4922 feet)


Audible Noise:

55dB ETS 300 753 Class 3.1


Standards

Safety Compliance:

EN 62040-1-1/IEC 62310-1/UL-1778


Certification: CE,

UL


RoHS: Compliant

EMC: EN55022

Class

B


MTBF:

>200,000 hours as per Telcordia SR-332