Inverter

Maintenance

(P2)

Mains

Inverter

Load

Backfeed Relay

Bypass Relay

MBS Main Contact1

MBS Main Contact2

SCR1

SCR2

Inverter Maintenance:

Mains AC powers the load
through the static switch

Inverters are on, but do not
provide any load power

Inverter can be removed from
the system, but the static
switch can not

MBS can be switched from P2
to P1 and P3 position

SCR2 open, SCR1 and Back-
feed Relay closed

When SCR2 short, the static
switch will keep the off-line
mode

Normal Operation:

Mains

Inverter

Load

Backfeed Relay

Bypass Relay

MBS Main Contact1

MBS Main Contact2

SCR1

SCR2

1. Mains priority

Mains AC powers the load
through the static switch

MBS can be switched from P3
to P2 and P4 position

SCR2 open, SCR1 and Back-
feed Relay closed

When the main’s voltage or
frequency is abnormal, and the
inverter is normal, the static
switch should transfer to on-
line mode

When SCR2 is short, the STS
will keep the off-line mode

Normal

Operation

(P3)

Mains

Inverter

Load

Backfeed Relay

Bypass Relay

MBS Main Contact1

MBS Main Contact2

SCR1

SCR2

2. Inverter priority

Inverter powers the load
through the static switch

MBS can be switched from P3
to P2 and P4 position

SCR1 open, SCR2 and Back-
feed Relay closed

When the inverter’s voltage or
frequency is abnormal, and the
mains is normal, the static
switch should transfer to off-
line mode

When SCR1 is short, the STS
will keep the on-line mode,
and the Back-feed relay will
open