Specifications for INEX 100A STS Module and MBS+PDU

Argus Technologies Ltd.

019-061-B1 Rev A WC

Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved.

Page 1 of 2

DC Auxiliary Power Input

Operating Range:

40 to 60Vdc within rated limits


AC Input

Voltage Range:

110/115/120Vac: 89 to 138Vac
208/220/230/240Vac: 176 to 276Vac


Over Voltage Threshold:

276 / 138Vac


Under Voltage Threshold:

176 / 89Vac


Back-feed Protection:

Comply with safety requirement


Redundant Power Supply Design:

Startup by priority source or alternative


NOTE: the over/under voltage must be set by controller, if there is no additional setting, STS will adopt the widest range

to set over/under voltage in order to guarantee its performance, for 110/115/120Vac system, the range is 89Vac
(under voltage point) to 138Vac (over voltage point), for 208/220/230/240Vac system, the range is 176Vac (under
voltage point) to 276Vac (over voltage point). But once the STS is set by user, it will keep the setting whether a
controller exists or not, until such time that the STS is set by user again or next time the source connected to STS
is changed from 120V (110/115/120) to 230V (208/220/230/240) or 230V (208/220/230/240) to 120V
(110/115/120).


AC Output

Waveform:

Sinusoidal


Nominal Output Voltage:

Same as mains AC or the output of inverter modules


Permissible Frequency Area:

Max. ±2.5% (synchronize area of inverter)


Transfer Time:

Typical 1/4 cycle, DIN VDE 0558 Part 5; IEC 146-4


Rated Power:

100A for 120 / 230Vac


Operation Methods:

Inverter priority / Mains priority


Over Load Capability:

1.2 x Inom ≥ 20s
1.6 x Inom ≥ 5s
3200A ≤ 10ms (Mains bypass)
Inom = 100A