2 terminal x1.a & line connection, L1l2 l3, Installation and connection – DE-STA-CO F5-B AC Inverter Drive User Manual

Page 15

Advertising
background image

15

Installation and Connection

Line connection
230 V 3-phase
& 460 V 3-phase

Line connection
230 V 1-phase

X1.A

L2

L1

GND

- -

+ +

L3

L2/N

L1

PE

X1.A

L3

L2

L1

GND

- -

+ +

L3

L2/N

L1

PE

A Housing:

7

L1L2

L3

++

--

E

A Housing:

Steps to wire the connectors

•Remove the connector from the inverter housing
by grasping it firmly and pulling straight out
•The maximum wire gauge is 14 awg or 1.5mm
•Strip the insulation back 0.25 in (7mm)
•The use of ferrules is optional
•Press a flathead screwdriver into the
upper slot
•Slide the bare wire into the lower slot
•Remove the screw driver and check
the wire connection by pulling back
on the wire to ensure it stays

3.3.2 Terminal X1.A & Line Connection

PE

L1

N/L2

L3

++

--

Terminal strip X1A
Provides connections for:
• 230 VAC/1-phase (L1,L2/N)
• 230 VAC/3-phase (L1, L2/N,L3)
• 230 VAC/DC-Supply 250...370 V DC (++, --)
• 460 VAC/3-phase (L1, L2, L3)
• 460 VAC/DC-Supply 420...720 V DC (++, --)

A Housing:

Advertising