Error diagnosis – DE-STA-CO F5-B AC Inverter Drive User Manual

Page 48

Advertising
background image

48

E.dOH ERROR drive overheat

9

Error: Overtemperature signal from motor temperature sensor.
Error can only be reset at E.ndOH, when sensor resistance
decreases. Causes:
• resistor at the terminals T1, T2 >1650 Ohm
• motor overloaded
• line breakage to the temperature sensor

E.nEd

no ERROR detected

10

No defined error recognized (should not occur)

E.ndOH no ERROR drive overheat

11

No longer overtemperature of motor Temperature SENSOR,
SENSOR is again low-resistance.

E. PU

ERROR power unit

12

Error: General power circuit fault

NO.PU power unit not ready

13

Power circuit not ready

E.PUIN ERROR power unit invalid

14

Error: Software version for power circuit and control card are
different. Error cannot be reset.

E.LSF

ERROR load shunt fault

15

Error: charging relay does not close after the DC bus voltage
reaches its normal operating level. Occurs for a short time
during the switch-on phase, but must automatically be reset
immediately (after 10 sec's E.UP). If the error message re-
mains, the following causes may be applicable:
• load-shunt defective
• input voltage incorrect or too low
• high losses in the supply cable
• braking resistor incorrectly connected or damaged
• braking module defective

E. OL

ERROR overload

16

Error: Overload error can only be reset at E.nOL, if OL-counter
has again reached 0%. Occurs, if an excessive load is applied
longer than the permissible time (see technical data). Causes:
• poor control adjustment (overshooting)
• mechanical fault or overload in the application
• inverter not correctly sized for application
• motor incorrectly wired
• encoder damaged

E.nOL no ERROR overload

17

No more overload, OL-counter has reached 0%; after the error
E.OL a cooling phase must elapse. This message appears
upon completion of the cooling phase. The error can be reset.
The inverter must remain switched on during the cooling
phase.

E.buS

ERROR bus

18

Error: Adjusted time (Watchdog) of communication between
operator and communication bus has been exceeded.

E.OL2 ERROR overload 2

19

Error: Overload while running below 3 Hz. Can only be reset at
E.nOL2, if cool-down time has elapsed.

E.nOL2 no ERROR overload 2

20

No more overload, the cool-down time is terminated.

E.EEP E. EEPROM defective

21

Error: EEPROM defective. After reset the error is repeated.
(parameter values changed are erased in the EEPROM)

Error Diagnosis

Advertising