As a momentary signal is sent to INPUT 14 the drive indexes until it
receives a signal on INPUT 11. On reception of signal on INPUT 11 the
drive either decelerates and stops or the stop point is delayed for a
positioning stop. This depends on the value entered in CP.27.

3.5.8 Operation

Explanation

Installation and Connection

ST

(pin 16)

Quick Stop

(pin 10)

Start

(pin 14)

Stop

(pin 11)

Motor

(RPM)

Drive reactivates into indexing mode - motor stopped condition

or Quick Stop mode depending on Quick Stop input!

ST: Loss of signal shuts off the motor voltage - the motor will coast to a stop

Quick Stop: Ignored

Start pulse: Ignored

Stop signal: Ignored

ST

(pin 16)

Quick Stop

(pin 10)

Start

(pin 14)

Stop

(pin 11)

Motor

(RPM)

ST: Must be high

Quick Stop: Loss of signal decelerates the load to a stop

Start pulse: Ignored

Stop signal: Ignored

Drive reactivates into indexing mode - motor stopped condition!

In the index mode, the start pulse
takes priority over the stop pulse.

Disabled Mode - Motor Voltage Off

6ms minimum pulse

6ms minimum delay between
Quick Stop and Start

6ms minimum
pulse

Quick Stop Mode - Stop Motor