Technical data

Type 2101

6.4. operating conditions

Observe permitted ranges on the type label of the device!

6.4.1. Temperature ranges

The globe valve is suitable for steam sterilization.

actuator

size

actuator

material

medium

(for ptfe seal)

environment

1)

ø 50 mm

PPS

-10 ... +185 °C

0 ... +60 °C

2)

0 ... +100 °C

3)

ø 70 mm
ø 90 mm
ø 130 mm

Tab. 1: Temperature ranges

1)

If a pilot valve is used, the max. ambient temperature is
+55 °C.

2)

Pilot air ports with push-in connector

3)

Pilot air ports with threaded bushing

6.4.2. Pressure ranges

actuator size

maximum pilot pressure

4)

ø 50 mm

10 bar

ø 70 mm
ø 90 mm

ø 130 mm

7 bar

Tab. 2: Pressure ranges

4)

For the device version ø 70 / Orifice 50 / MC 13 the
max. permitted pilot pressure is limited to 7 bar.

minimum pilot pressure: flow below the seat
(medium flow against the closing direction of the valve)
Required minimum pilot pressure P

min

with control function A:

actuator

size [mm]

50

70

90

130

≤ DN 50

130

≥ DN 65

p

min

[bar]

5,2

4,8

5,0

5,0

5,6

The required minimum pilot pressure P

min

with control function B and I

(flow below the seat) is dependent on the pressure of the medium

5)

.

minimum pilot pressure: flow above the seat
(medium flow with the closing direction of the valve)
The required minimum pilot pressure P

min

with control function A

(flow above the seat) is dependent on the pressure of the medium

5)

.

5)

The pressure diagrams are in the operating instructions
on the Internet:

www.burkert.com

english

Advertising