Echo curve

In this menu item you simulate a user-defined level or pressure value
via the current output. This allows you to test the signal path, e.g.
through connected indicating instruments or the input card of the
control system.

The following simulation variables are available:

l

Percent

l

Current

l

Pressure (with pressure transmitters)

l

Distance (with radar and guided microwave)

With Profibus PA sensors, the selection of the simulated value is made
via the "Channel" in the menu "Basic adjustments".

How to start the simulation:

1

Push [OK]

2

Select the requested simulation variable with [->] and confirm with
[OK]

.

3

Set the requested numerical value with [+] and [->].

4

Push [OK]

The simulation is now running, with 4 … 20 mA/HART a current is
outputted and with Profibus PA or Foundation Fieldbus a digital value.

How to interrupt the simulation:

à Push [ESC]

Information:
The simulation is terminated automatically 10 minutes after the last key
has been pushed.

Simulation

Start simulation?

With the reset function, modified values are reset. Three subfunctions
are available:

l

Basic adjustment

-

Reset the values modified with the indicating and adjustment
module to the sensor-specific basic setting

l

Factory setting

Service/Simulation

Service/Reset

Indicating and adjustment module

15

5

Setup - Sensors up to software 3.99

41787

-