Burkert Type 8186 User Manual

Page 21

Advertising
background image

In Multidrop mode, up to 15 sensors can be operated on one two-wire
cable. An address between 1 and 15 must be assigned to each
sensor.

7

)

In this menu item you determine the HART mode and enter the
address for multidrop.

HART mode

Standard
Address 0

The default setting is standard with address 0.

7

)

The 4 … 20 mA signal of the HART sensor is switched off. The sensor
consumes a constant current of 4 mA. The measuring signal is transmitted
exclusively as digital HART signal.

Indicating and adjustment module

21

5

Setup - Sensors up to software 3.99

41787

-

EN

-

120316