In Multidrop mode, up to 15 sensors can be operated on one two-wire
cable. An address between 1 and 15 must be assigned to each
sensor.
7
)
In this menu item you determine the HART mode and enter the
address for multidrop.
HART mode
Standard
Address 0
The default setting is standard with address 0.
7
)
The 4 … 20 mA signal of the HART sensor is switched off. The sensor
consumes a constant current of 4 mA. The measuring signal is transmitted
exclusively as digital HART signal.
Indicating and adjustment module
21
5
Setup - Sensors up to software 3.99