Installation

3.3.1

PHOSPHAX sc analyzer power supply

Refer to the PHOSPHAX sc manual.

3.4

sc1000 controller connection

Connect the SUB-D plug supplied to a dual-core, sheathed data cable (signal or bus
cable). For further information regarding the data cable connection, refer to the enclosed
assembly instructions.

3.5

Flow rate signal connection

If a flow rate measurement signal of 4 to 20 mA is available, connect it to the analog input
of the RTC module.

3.6

Connection to the automation unit on the plant side

Depending on the variant and option, the RTC101 P-Module is equipped with various
components that must be connected to the plant's automation unit.

The volumetric flow rate is provided to the RTC module as a 0/4 to 20 mA signal for all
variants and options.

The precipitant volume to be metered is delivered by the RTC module as a 0/4 to
20 mA signal for all variants and options.

Alternatively, the precipitant volume can also be output by the fieldbus variants
provided by the sc1000 (see sc1000 operating instructions).

The RTC module supplies the digital output signal for activating the precipitant pump
at 0 V or 24 V.

The RTC module supplies a collective fault message at 0 V (fault) or 24 V (device
functional).

Table 2 Signal allocation of individual components of the RTC module

RTC module options

Component

Name

Connection

Signal

Function

1-channel

2-channel

2-fold digital output

1

1

Ground to connections 3 and 7 or equal to voltage supply

KL2032

1

+24 V/0 V

Precipitant pump on/off

X

5

+24 V/0 V

No fault/fault

X

4-fold digital output

1

KL2134

1

+24 V/0 V

Precipitant pump 1 on/off

X

5

+24 V/0 V

No fault/fault in channel 1

X

4

+24 V/0 V

Precipitant pump 2 on/off

X

8

+24 V/0 V

No fault/fault in channel 2

X

Single analog output

KL4011

1(+) 3(-)

+24 V/0 V

Precipitant pump dosing rate

X

2-fold analog output

KL4012

1(+) 3(-)

+24 V/0 V

Precipitant pump 1 dosing rate

X

5(+) 7(-)

+24 V/0 V

Precipitant pump 2 dosing rate

X

1-fold analog input

KL3011

1(+) – 2(-)

0/4 to 20 mA

Feed volume flow Channel 1

X

X

2-fold analog input

KL3011

1(+) – 2(-)

0/4 to 20 mA

Feed volume flow Channel 2

X