5 1-channel closed-loop control – Hach-Lange WTOS P-RTC User Manual

Page 24

Advertising
background image

24

Parameterization and operation

4.3.5

1-channel closed-loop control

1-channel closed-loop control

CONFIGURE

SELECT SENSOR

Select the sensor installed for the closed-loop control (refer to

Section 4.4, page 29

).

CLOSED-LOOP

SETPOINT PO4-P

Desired orthophosphate value in effluent (refer to

4.5.1, page 31

)

[mg/L]

GAIN P CONTR.

Proportional gain of the closed-loop control (refer to

4.5.5, page 32

)

INTEGRALTIME

Integral time of closed-loop control (refer to

4.5.5, page 32

)

[min]

DERIVATIVE TIME

Derivative time of closed-loop control (refer to

4.5.5, page 32

)

[min]

MIN DOS RATE

Minimum flow rate of dosing pump

[L/h]

PRESELECT PROG

Programs 1 to 4 (refer to

4.1, page 15

)

PROFILE

Active

when a measurement signal fails

Q-PROFILE

Daily profiles (2 h average) of waste water influent according to feed measurement
signal

[m³/h]

P-PROFILE

Daily profiles of PO

4

-P concentrations, 2 h average (see

4.5.4, page 32

)

[mg/L]

WEEK PROFILE

Percentage daily averages of the phosphate load (refer to

4.5.4, page 32

)

[%]

IN- OUTPUTS

DOSING PUMP

MIN PUMP RANGE

Lower threshold of flow rate range

[L/h]

MAX PUMP RANGE

Upper threshold of flow rate range

[L/h]

0/4...20MA

Selection of transfer range according to pump input

CONTROL CYCLE

Control cycle comprising on- and off-time (see

4.5.6, page 33

)

[s]

MIN RUNTIME

Minimum on-time of pump (refer to

4.5.6, page 33

)

[s]

FLOW RATE

MIN Q-INFLUENT

Minimum flow rate in inlet according to measurement signal

[m³/h]

MAX Q-INFLUENT

Maximum flow rate in inlet according to measurement signal

[m³/h]

0/4...20MA

Transfer range of 0/4–20 mA current loop, as set in the connected flow measuring instrument.

MIN RET SLUDGE

Minimum flow rate of return activated sludge pump(s) (refer to

4.5.7, page 34

)

[m³/h]

MAX RET SLUDGE

Maximum flow rate of return activated sludge pump(s) (refer to

4.5.7, page 34

)

[m³/h]

Q RET RATIO

Ratio between measured flow rate and return activated sludge volume, for a return
activated sludge volume proportional to the measured flow rate (Refer to

4.5.7,

page 34

)

[%]

Q INFL SMOOTH

Smoothing of influent signal (refer to

4.5.7, page 34

)

Advertising