Section 1

Specifications

Subject to change without notice.

Industrial Personal Computer (IPC), (Embedded PC)

Processor

Pentium

®1

, MMX compatible, 500 MHz clock rate

Flash memory

2 GB compact flash card

Internal working memory

256 MB DDR-RAM (not expandable)

Interface

RJ 45 (Ethernet), 10/100 MBit/s

Diagnostic LEDs

Power, LAN speed, LAN activity, TC status, flash access

Expansion slot

Compact flash type II slot with ejection mechanism

Clock

Internal, battery-buffered clock for time and date (battery can be
replaced)

Operating system

Microsoft Windows

®2

CE or Microsoft Windows Embedded Standard

Control software

TwinCAT PLC Runtime or TwinCAT NC PTP Runtime

System bus

16 Bit ISA (PC/104 standard)

Power supply

Via system bus (through power supply module CX1100-0002)

Max. power loss

6 W (including the system interfaces CX1010-N0xx)

Analog input

4–20 mA for flow rate measurement

Internal resistance

80 Ohm × diode voltage 0.7 V

Signal current

0–20 mA

Common mode voltage (U

CM

)

35 V max.

Measurement error (for entire measurement
range)

< ± 0.3 % (from measurement range end value)

Electrical surge resistance

35 VDC

Electrical isolation

500 V

eff

(K-bus/signal voltage)

Analog output

4–20 mA for dosing pump

Number of outputs

1

Power supply

24 V DC via power contacts

(alternatively 15 V DC with bus terminal KL9515)

Signal current

0–20 mA

Working resistance

< 500 Ω

Measurement error

± 0.5 LSB linearity error

± 0.5 LSB offset error

± 0.1, % (relative to the measuring range end value)

Resolution

12 bit

Conversion time

~ 1.5 ms

Electrical isolation

500 V

eff

(K-bus/signal voltage)