GROUNDING

Grounding the AeGIS 8000 System is essential. Please comply with all local ordinances and industry standard procedures to
ensure a complete and safe ground. Recommended earth grounds are:

• Use 16-gauge solid wire for grounding.
• Installing a ground steel rod from the steel enclosure to the earth ground, use the same grounding point on all

systems for best ground.

• Installing a solid heavy gauge wire from the AeGIS steel enclosure to a water pipe.
• Connecting the AeGIS steel enclosure to any earth grounded steel metal.

TELEPHONE LINE

Always use AeGIS AC/Telephone Surge Protector (ASP1) to protect your investment.

• Twisted pair category 5 is the minimum requirement if the distance less than 100 feet. Shielded wires are

recommended to avoid radio reception or any other noise problems. If the distance is more than 100 feet,
2-conductors, 18 gauge shielded stranded is recommended. Ground one end of the shielded to earth ground.
See installation instruction if ASP1 Surge Protector is used.

• If a PBX line is used, the AeGIS system must be connected to the analog extension port to dial within the

extension.

Do not connect the AeGIS to the PBX digital extension port.

Note: The system can only be programmed to dial another extension or the outside line, it cannot dial both. If the

system is programmed to dial the outside line, then the system cannot be used to dial another extension.

DOOR STRIKE OR ELECTRICAL STRIKE

The AeGIS 8000 Series come with two on board relay: Two Normally Open (NO) and Two Normally Closed (NC).

• 10 Ampere 120 VAC or
• 10 Ampere 24 VDC or
• 7 Ampere 250 VAC

See figure 2.1 for door strike wiring diagram. See door strike or electrical strike manual for wiring requirements.

Note:

Some door strikes are creating electrical, magnetic noise or spikes and could create problem to the system's
memory. Although the system's relay has built-in filtration circuit, installing an isolation relay is recommended if the
system is experiencing with looses memory. Use separate power supply for the isolation relay.

POSTAL LOCK

The AeGIS 8000 Series comes with pre-wired "Normally Open" postal switch as shown on figure 2.2(a). If the postal switch
is pressed, the gate will open. If you need "Normally Closed" postal switch, see figure 2.2(b).
The postal lock is not included. You have to purchase the postal lock from your local post office. The postal switch can be
used for other purposes such as infra-red free exit sensor or switch, card reader, etc.

Fig 2.2 (a)

Fig 2.2 (b)

1

2

3

4

Pach and Company

Chapter 2

Page 5

AeGIS 8000 Series

INSTALLATION

Advertising