Installation, Components requiring ventilation to the outdoors – Fulton Vantage (VTG) Fully Condensing Hydronic Boiler User Manual

Page 19

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 2

VTG-IOM-2013-0815

INSTALLATION

2-13

burner confi gurations do not support vent limiters and
will need to be vented if required by the AHJ.

17. Vantage boilers with the SKP25 fuel train are in

compliance with CSD1 and CSA. This confi guration is
also compliant with IRI, which has been replaced by GE
GAP. NFPA 85 confi guration is available as an option to
comply with local codes or regulations that specifi cally
require a vent valve.

18. Please note that custom confi gurations or other off

standard projects may utilize alternate fuel trains. For
these situations, refer to submittal drawings.

19. Ensure the burner will be supplied with suffi

cient

ventilation and uncontaminated air for proper

combustion. Air contaminants include, but are not
limited to, chlorides, halogens, fl ourocarbons, and
construction dust. Refer to appropriate jurisdictional
codes.

Components Requiring Ventilation to the

Outdoors

Although there are custom fuel train requirements available
that do not include components requiring ventilation to the
outdoors, many Vantage fuel trains will require a vent line on
the gas pressure regulator.

Follow the recommendations of the manufacturer of the
gas pressure regulator for specifi c instructions. General

TABLE 3 - NOMINAL PIPE SIZE

Nominal
Pipe Size

ID

Equivalent Pipe Length

Max Capacity in ft3 of natural gas per hour. Pressure drop of
0.5”wc/Equivalent length of pipe (feet)

Inch (mm)

Inch (mm)

90 Elb
Feet
(meter)

Tee
Feet
(meter)

20

40

60

80

100

150

200

1-1/4 (31.75)

1.380 (35.05)

3.45 (1.05)

6.9 (2.10)

950

-----

-----

-----

-----

-----

-----

1-1/2 (38.1)

1.610 (40.89)

4.02 (1.22)

8.04 (2.45)

1460

990

810

-----

-----

-----

-----

2 (50.8)

2.067 (52.50)

5.17 (1.57)

10.3 (3.13)

2750

1900

1520

1300

1150

950

800

2-1/2 (63.5)

2.469 (62.71)

6.16 (1.87)

12.3 (3.74)

4350

3000

2400

2050

1850

1500

1280

3 (76.2)

3.068 (77.92)

7.67 (2.33)

15.3 (4.66)

7700

5300

4300

3700

3250

2650

2280

4 (101.6)

4.026 (102.26)

10.10 (3.07)

20.2 (6.15)

15800

10900

8800

7500

6700

5500

4600

6 (152.4)

6.07 (154.17)

10.10 (3.07)

23.60 (7.19)

-----

-----

-----

-----

20200

16503

12766

8 (203.2)

7.98 (202.69)

13.30 (4.05)

29.10 (8.86)

-----

-----

-----

-----

41200

33660

29128

FIGURE 6 - FULTON PH NEUTRALIZING KIT (WITHOUT PUMP)