Installation – Fulton Vantage (VTG) Fully Condensing Hydronic Boiler User Manual

Page 23

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 2

VTG-IOM-2013-0815

INSTALLATION

2-17

A

B

7

3

5

2

7

4

6

6

5

V

P

+H

-H

3

15

16

Supplied with
Boiler

FIGURE 10 - FUEL SUPPLY

Figure 10 Legend and Notes

H Pump/Foot valve height diff erence

L Piping length

O Inside Pipe Diameter

2 Pump

3 Filter

4 Manual On/Off Valve

5 Suction Line

6 Foot Valve

7 Return Line

V Max distance 13 ft (3.94 m)

Fuel Supply: The pumping unit of the burner

is equipped with a self-priming pump capable

of feeding itself within the limits listed in tables

below.

The tank is higher than the pumping unit (A):

The distance “P” must not exceed 33 ft (10 m)

in order to avoid subjecting the pump’s seal to

excessive strain; the distance “V” must not exceed

13 ft (3.94 m) in order to permit pump self priming

even when the tank is almost completely empty.

The tank is lower than the pumping unit (B):

Pump suction pressures higher than 13”Hg for

Suntec oil pump and 15”Hg for Webster 2 Stage

22R oil pump must not be exceeded. This is

because at higher levels, gas is released from the

fuel and the pump starts making noise and its

working life-span decreases.

It is good practice to ensure that the return and

suction lines enter the pumnp from the same

height to reduce risk of priming failure.

RLS-160E (for use with VTG-6000)

+H

-H

(ft)

L(ft)

O (inch)

1/2”

5/8”

+13

197

263

+10

164

230

+6.6

132

197

+4.8

115

181

+3.3

99

164

+1.6

82

148

0

66

132

-1.6

59

115

-3.3

49

99

-4.8

43

82

-6.6

33

66

-10

16

33

-13

- 20

RLS-100-130E (for use with VTG-2000 to VTG-4000)

+H

-H

(ft)

L(ft)

O (inch)

3/8”

1/2”

5/8”

+13

100

210

320

+10

88

180

320

+6.6

75

155

320

+3.3

68

140

320

+1.6

52

110

270

0

45

98

240

-1.6

39

85

200

-3.3

26

55

140

-6.6

19

42

104

-10

-

13

36