Operation, Setting pilot (for boilers equipped with a pilot) – Fulton Vantage (VTG) Fully Condensing Hydronic Boiler User Manual

Page 43

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

3-7

SECTION 3

VTG-IOM-2013-0815

OPERATION



ã

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

step will be shown as PWLogin > AccessServ for the remainder of this
section.

4. Enter the service passwords using the arrow key. The password is case

sensitive. The case of a letter can be changed by pressing the other
arrow key. (For example, if you used the right arrow key to get the letter
A, press the left arrow key to get a. After you have pressed Enter on the
last character of the password, press Enter on the last character of the
password, press Enter once more to accept the password. If you do not
have the password, contact your Fulton Authorized Representative to
perform the changes.

5. Select Params&Display. Press Enter. Select RatioControl. Press Enter. Select

ProgramStop. Press Enter. Change the Program Stop to 44 Interv1 by using
the arrow keys. Confi rm the change by pressing Enter. This will set the
burner management system to a ‘pilot hold’ setting.

6. Verify that the current valve “curr” changes to 44 Interv 1. The full list of

program stops are:

» 24-Air damper in the pre-purge position

» 36-Ignition position (before pilot ignition)

» 52-Ignition position (after main burner ignition)

» 72-Air damper in the post-purge position

7. Press Escape four times to get back to the main menu.

8. Under ManualOperation > Setload, change the load to 0% by using the

arrow keys. Press enter and verify the 0% has been acknowledged in the
“curr” fi eld.

9. Press escape once to get back to the ManualOperation menu.

10. Under

Auto/Manual/Off , change the operation to Burner On by using the

arrow keys. Press enter and verify that “Burner On” is acknowledged in the
current fi eld.

11. Press Escape twice to get back to the main menu.

12. Increase the setpoint on the temperature controller to create a heat

demand.

13. Turn the main burner switch to the Local or On position.

14. After several seconds the burner control will start its pre-ignition phase

and the blower will start. You can observe the status of the burner by going
to the main menu (by pressing Escape) then selecting OperationalStat >
NormalOperation.

Setting Pilot (For Boilers Equipped With a Pilot)

1. Following the Pre-Ignition phase (see previous section), the unit will purge

then drive to the ignition position and ignite. The burner control will stay at
this pilot hold stage so you can inspect and adjust the pilot as needed.