Operation, Operating temperatures and fuel selection, Temperature controller instructions – Fulton Vantage (VTG) Fully Condensing Hydronic Boiler User Manual

Page 47: Sc-500 temperature controller basic programming

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

3-11

SECTION 3

VTG-IOM-2013-0815

OPERATION



ã

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

10. Observe the status of the burner by going to OperationalStat >

NormalOperation.

11. Turn the main ON/OFF switch to OFF. The control will now post purge.

12. Follow the Pre-Ignition steps again to verify ignition with the new gas

pressures.

13. Turn the main burner switch to OFF. The control will now post purge.

14. Change the operation to Automatic under ManualOperation > Auto/

Manual/Off and press Enter and confi rm Automatic is entered in the
current fi eld.

15. Press Escape four times. Select PW Logout, the password is now logged

out.

16. Press Escape twice. Select OperationalStat > NormalOperation. The control

is now on the normal operational display screen.

17. The boiler is now ready to run. Adjust your setpoint on the temperature

control to the desired temperature and turn the main ON/OFF switch to
ON for the burner to operate.

Operating Temperatures and Fuel Selection

Use Table 6 to determine minimum return water temperature requirements:

TABLE 6 - MINIMUM RETURN WATER TEMPERATURES

Fuel

Minimum Return Water Temperature

Natural Gas

No minimum return water temperature

Propane

No minimum return water temperature

#2 Fuel Oil

140°F (60°C)

B100 Bio-Diesel

100°F (38°C)

#2 Fuel Oil with guaranteed <15
ppm Sulfur

100°F (38°C)

Digester Gas/Alternative Fuels

Consult Factory

Temperature Controller Instructions

The Siemens LMV37 and LMV51 controls may be paired with a temperature
controller. Options include the SC-500 Temperature Controller, the Yokogawa UT
32A, and the Siemens RWF40.

SC-500 Temperature Controller Basic Programming

CHANGE SET POINT

1. Set Point Mode is accessed through the switch selection or BMS screen

selection.

Advertising