Installation – Fulton Vantage (VTG) Fully Condensing Hydronic Boiler User Manual

Page 22

Advertising
background image

© The Fulton Companies 2013

INSTALLATION

VTG-IOM-2013-0815

SECTION 2

2-16

Figure 9 Notes

Characteristic

Connection

1

Suction

3/8” NPT (Piped in the Field)

2

Return

3/8” NPT (Piped in the Field)

3

Pressure Gauge Attachment

G 1/8” (Completed at Factory)

4

Vacuum Gauge Attachment

G 1/8” (Completed at Factory)

5

Pressure Regulator

6

Outlet to Burner

¼” NPT (Completed at Factory)

Minimum Delivery Rate at 174

PSI Pressure

54 GPH (204.41 LPH)

Delivery Pressure Range

145 – 290 PSI (997.7 - 1999.5 k Pa)

Maximum Suction

13 “ Hg

Oil Viscosity Range

2.8 – 75 cSt

Maximum Fuel Oil

Temperature

140 F (60 C)

Maximum Suction and Return

Pressure

29 PSI (199.9 kPa)

Pressure Calibration at the

Factory

198-200 PSI (1365 - 1379 kPa)

Filter Mesh Width

0.006 Inches (0.15 mm)

FIGURE 9 - OIL PUMP DETAILS (VTG-2000 TO VTG-4000)

B

C

D

E

FIGURE 8 - OIL PUMP LOCATION (VTG-2000 TO VTG-4000)

Advertising