Heater will turn on at 155 F (68 C). Press the PGM button to enter value.

4. Press the EXIT button to return to default display.

SET BOILER OFF TEMPERATURE

1. Press and hold the PGM button for 3 seconds. A number in red and the

letters AL in green will appear.

2. Use PGM button to scroll down to HYS.3.

3. Use the arrow buttons to change HYS.3 to the value desired. This value is a

additive diff erential from set point at which the burner will be turned on.
I.e. SP1 + HYS.3 = Heater Off Temperature. Ex. SP1 = 160, HYS.3 = 5 Heater
will turn off at 165 F (73 C). Press the PGM button to enter value.

4. Press the EXIT button to return to default display.

SET PROPORTIONAL BAND, INTEGRAL AND DERIVATIVE VALUES

1. Press and hold the PGM button for 3 seconds. A number in red and the

letters AL in green will appear.

2. Use the PGM button to scroll down to Pb1.

3. Use the arrow keys to change Pb1 to the value desired. The higher this

number is, the sooner the heater will begin to drop to low fi re. The smaller
this number is, the longer the heater will remain at high fi re before
dropping to low fi re. Press the PGM to enter value.

4. Use the PGM button to scroll down to dt.

5. Use the arrow keys to change dt to the desired value. This value must be

¼ the value in rt. The smaller this number is, the quicker the heater will
anticipate and react to changes in temperature. Press the PGM button to
enter value.

6. Use the PGM button to scroll down to rt.

7. Use the arrow keys to change rt to the desired value. The smaller this

number is, the quicker the heater will anticipate and react to changes in
temperature. Press the PGM button to enter value.

8. Press the EXIT button to return to default display.

Access to Variable Speed Drive Blower Motor

(Models VTG-3000LE, VTG-4000LE)

NOTE:

Some Fulton Vantage Low Emissions Designs include a Variable

Frequency Drive (VFD). The VFD is a Telemechanique Altivar 21 style.

The Variable Speed Drive programs are password protected and should only be
accessed by factory-trained personnel. Please contact your authorized Fulton
representative for assistance.