FEC AFC1500 User Manual

Page 38

Advertising
background image

Indication LED

Critical Link Failure

Red solid

Connection Time Out

Red flashing

On-line, link OK, connected.

Green solid

On-line but not connected.

Green flashing

Not Powered / Not Online

Off

Network Status LED
(#3)

Unrecoverable module fault

Red solid

Minor Recoverable fault

Red flashing

Device Operational - no errors

Green solid

No Power

Off

Module Status LED
(#2)

Status LEDs (#1 & 4 not used)

Address 63

ON

ON

ON

ON

ON

ON

Address 62

OFF

ON

ON

ON

ON

ON

Address 61

ON

OFF

ON

ON

ON

ON

.

.

.

.

.

.

.

Address 3

ON

ON

OFF

OFF

OFF

OFF

Address 2

OFF

ON

OFF

OFF

OFF

OFF

Address 1

ON

OFF

OFF

OFF

OFF

OFF

Address 0

OFF

OFF

OFF

OFF

OFF

OFF

MAC ID

SW-8

(LSB)

SW-7

SW-6

SW-5

SW-4

SW-3

MAC ID setting (Board switch)

This switch must be set before power is on, and cannot be changed during
operation.

Reserved

ON

ON

500K

OFF

ON

250K

ON

OFF

125K

OFF

OFF

Baud rate

SW-2

SW-1

Baud rate setting (Board switch)

This switch must be set before power is on, and cannot be changed during
operation.

Chapter 3: Control Interfaces

38