Termination
Termination of the fieldbus requires a terminating resistor at each end of the
fieldbus. A termination switch is provided on the Profibus-DP interface
board. Set the switch to “ON”, if termination is required. If external
terminators are used, the switch must be in the off position.

GSD File
Each device on a Profibus network is associated with an GSD file containing
all necessary information about the device to be connected. The network
configuration program uses this file during configuration of the network.
The GSD file associated with the FEC device can be downloaded from the
FEC website. www.fec-usa.com (File : hms_1003.gsd)
Direct link:www.fec-usa.com/fecusacomnew/support/index.htm
(the file can also be downloaded directly from HMS - www.hms.se)

The module only supports cyclic I/O
data transmission.

Data transmission

244bytes In, 244 bytes out max.
416 total bytes max.

Maximum Cyclic I/O Size

Ver. 1.10

Protocol Version

Master/Slave - EIA RS485

Communications Type

Shielded Copper Twisted Pair or fiber
optic

Cable

200m max. at 1.5Mbit/s extendable with
repeaters.

Distance

126 Note:Node 126 is reserved for
commisioning purposes only

Nodes

9.6K - 12M baud - autoselected

Speed

Profibus Specifications

Connected to PE

Shield

Housing

Not Connected

Pin 9

Negative RxD/TxD according to RS485 Spec.

A- Line

Pin 8

Not connected

Pin 7

Isolated +5V from RS 485 side

+5V Bus

Pin 6

Isolated GND from RS 485 side

GND Bus

Pin 5

Request to send

RTS

Pin 4

Positive RxD/TxD according to RS485 Spec.

B- Line

Pin 3

Not Connected

Pin 2

Not Connected

Pin 1

Profibus connector - D-Sub

Chapter 3: Control Interfaces