FEC AFC1500 User Manual

Page 41

Advertising
background image

Indication LED

Module is offline on the fieldbus

Red

Module is not offline

Off

Off- Line
LED #3

Module online and communication OK

Green

Module not online

Off

On-Line
LED #2

Error in initialization of Profibus
communication ASIC

Flashing Red -
4sec

Error in user parameter data -
parameter length/content does not
match network length/content

Flashing Red -
2sec

Config. Error - in/out length set at
module intialize does not match
length in network config.

Flashing Red -
1sec

LED #4

Indicates faults on fieldbus side

Red

Fieldbus Diagnostics

Status LEDs

LED #1- Not Used

Node Address
Before configuring the Profibus-DP module the node address has to be set.
This is done with two rotary switches on the module which can set the node
address 1-99 in decimal format. The Upper rotary switch (closest to the
D-sub) sets the “ten” digit (X 10), and the bottom rotary switch sets the single
digit. Example: To set node 37, place the “ten” switch on 3, and the single
digit switch on 7.
This switch must be set before power is on, and cannot be changed during
operation.

Configuration
FEC Profibus I/O configuration is programmable using the AFC User Console
software. I/O can be set as required by the application according to parameter
limits set forth by the GSD (Profibus) configuration file. The AFC Software
allows configuration of the number of I/O in the Multi Unit. Configuration of
the Profibus Master MUST match the configuration of the FEC Profibus
slave. In the Profibus Master set-up, input size and output size is set as “byte”

Chapter 3:

Control Interfaces

41