FEC AFC1500 User Manual

Page 46

Advertising
background image

Indication LED

Module Reading Data

Read Data

RD

Module Sending Data

Send Data

SD

Communication error at Station

ON - Flashing

Communication error at all Stations

ON - Steady

Normal

OFF

ERR

Module is Normal - Running

ON

Watchdog Timer error

OFF

RUN

Status LEDs

Configuration
Configuration of the CCLink system is done in the PLC Logic. It is essential
that this configuration matches the Dip Switch settings of the FEC CCLink
slave. FEC is considered a “Remote Device” in the PLC configuration. The
number of “Occupied Stations” set in the PLC must also match the Dip Switch
set-up. (Note: The last 16 output addresses are used by the CCLink
communication & cannot be used by the user) Below is an example of the
PLC configuration setting for the FEC Node in the CCLink network;

Command
[MOV H1306 D19]

Description
MOV = Move command
H = Hex number being used
1 = Remote Device (0= Remote I/O Station, 2= Intelligent Device)
3 = 3 Occupied Stations (3 x 32I/O = 96 Inputs & Outputs, (4 is max.))
06 = Station #6 (CCLink address, 64 max.)
D19 = PLC register which stores the configuration (could be any register #)

Note: This is only an example of the station setting configuration. Other
configuration must be completed in the PLC logic for proper operation. The
PLC configuration MUST match the settings of the FEC Dip Switches. The
communication link will not be established and the red “ERR” LED will be lit
if these settings do not match. Please review the Mitsubishi CCLink manual
#13J872 for further information.

Chapter 3: Control Interfaces