Warning, Operating instructions, Recovering refrigerant – Robinair 348012K Recovery, Recycling, Recharging Unit User Manual

Page 16

Advertising
background image

© 2000 Robinair, SPX Corporation

1 4

Diagram of Control Panel During Recovery

INST 0714

Recover

RECOVERING REFRIGERANT

WARNING

Always wear safety goggles when working with refrigerant. Read and

follow all warnings at the beginning of this manual before operating

the unit.

1. Connect the power cord to the back of the unit and plug into the proper

voltage outlet.

2. Turn on the MAIN POWER and empty the oil drain bottle located on the right

hand side of the unit.

3. Press

RECOVER

.

4. If 300 or more pounds of refrigerant has been recovered since the last filter-

drier change, the display reads REPLACE FILTER.

5. Connect the high and low side hoses to the A/C system service ports. For

R-134a, open the coupler valves.

6. Place both High and Low Side manifold valves in the Recover/Vacuum

position on the control panel.

7. If the system pressure is below 25 psi, the display reads LOW SYSTEM

PRESSURE until the pressure increases or the

START

button is pressed.

8. If the unit has refrigerant in the low-side plumbing, it begins the clearing

process and displays CLEARING. If you wish to skip the clearing operation or
stop the clearing prematurely, press

START

.

NOTE: An inaccurate recovery weight may result if the clearing operation is
not completed.

9. When the system has recovered to a vacuum level of approximately 13 in. Hg.,

the compressor automatically shuts off.

Operating Instructions

Valves

Open

Manifold Gauges

Manifold Gauges