348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit

USING THE SELECTION MENU

(continued)

4-a. TANK FILL (R-12 Users)

NOTE: If using a refillable tank, place the tank upside down and connect the
lowside service hose to the vapor valve.

Set SELECTOR switch to R-12:

1. Connect the 6" yellow adapter to the end of the low side service hose.

2. Connect the low side service hose to the source tank and open valve.

3. Select TANK FILL from the Selection Menu.

4. Press

ENTER

. Then press

START

and the tank automatically refills. The

unit stops when a sufficient amount of refrigerant has been transferred to the
ESV- or - the source tank is empty.

NOTE: Press

STOP

if you wish to stop fill before it completes.

5. Close the valve on the source tank.

6. Disconnect the 96" blue service hose from the adapter, then disconnect the

6" yellow adapter from the source tank.

7. Press

STOP

to exit.

Operating Guidelines

ESV

INST0710

Source

Tank

R-12

Low Side

Service Hose