4

IMPORTANT APPLICATION INFORMATION

4.1

MOTOR WITH EXTERNAL FAN

COOLING – Most totally enclosed fan-

cooled (TEFC) and open ventilated 3-phase

AC induction motors will overheat if used

beyond a limited speed range at full torque.

Therefore, it is necessary to reduce motor

load as speed is decreased.

Note: Some fan-cooled motors can be

used over a wider speed range. Consult

the motor manufacturer for details.

WARNING! Some motors have low

speed characteristics which cause

overheating and winding failure under light

load or no load conditions. If the motor is

operated in this manner for an extended

period of time, it is recommended that the

unloaded motor current be checked from

2 – 15 Hz (60 – 450 RPM) to ensure motor

current does not exceed the nameplate

rating. Do not use motor if the motor

current exceeds the nameplate rating.

It is recommended that the drive

be used with Inverter Duty or

TENV motors.

Inverter duty and most totally enclosed non-ventilated (TENV) motors can provide full rated torque over an

extended speed range without overheating. See Figure 5.

If external fan cooling is provided, open ventilated motors can also achieve an extended speed range at full

rated torque. A box fan or blower with a minimum of 100 CFM per HP is recommended. Mount the fan or

blower so the motor is surrounded by the airflow. See Figure 6.

4.2

ELECTRONIC MOTOR OVERLOAD PROTECTION – The drive contains Modified I

2

t Overload Protection.*

Part of this function consists of a Current Limit (CL) circuit, which limits the drive current to a factory preset

level of 160% of the rated drive current. The CL Trimpot is used to recalibrate the drive current from 60%

thru 200%. The Power Start™ circuit provides an overshoot function that allows most motors to develop

more than 200% of starting torque and breakdown torque.

Standard I

2

t is undesirable because it causes nuisance tripping. It allows a very high motor current to

develop and will turn the drive off after a short period of time. KB’s RMS Current Limit Circuit avoids this

nuisance tripping while providing maximum motor protection.

If the motor is overloaded to 120% of full load (75% of the CL setting), the I

2

t Timer starts. If the motor con-

tinues to be overloaded at the 120% level, the timer will shut down the drive after 30 minutes. If the motor is

overloaded to 160% of full load, the drive will trip in 6 seconds. See Section 11.6, on pages 22 and 23.

*UL approved as an overload protector for motors.

13

FIGURE 5 – MAXIMUM ALLOWED MOTOR TORQUE

VS

. SPEED

FIGURE 6 – OPEN VENTILATED MOTOR WITH EXTERNAL FAN COOLING

Motors

and TENV

Inverter Duty

Maximum

Allo

wed

Motor

To

rque (%)

TEFC and Open Ventilated

Motors

Fan Cooled

100

60

70

80

50

30

40

10

0

20

90

Motor Speed (%)

40

0

20

60

80

100

Open Ventilated Motor

Fan or Blower

(100 CFM Min.

per HP)

Airflow