5

MOUNTING INSTRUCTIONS

The drive is designed with a NEMA-1 / IP-40 enclosure for indoor use. It is recommended that the drive be

mounted vertically on a flat surface with adequate ventilation. Leave enough room below the drive to allow for AC

line, motor connections, and any other wiring that is required. Care should be taken to avoid extreme hazardous

locations where physical damage can occur. When mounting the drive in an enclosure, the enclosure should be

large enough to allow for proper heat dissipation so that the ambient temperature does not exceed 45°C (113 °F)

at full rating. See Figure 2, on page 10. A mounting template is included to facilitate mounting of the drive.

WARNING! Do not use this drive in an explosion-proof application.

6

ELECTRICAL CONNECTIONS

See Table 4, for terminal block wire and tightening torque specifications.

WARNING! Read Safety Warning, on page 5, before using the drive. Disconnect main power

before making connections to the drive. To avoid electric shock, be sure to

properly ground the drive.

Application Note: To avoid erratic operation, do not bundle the AC line and motor wires with each other or

with wires from signal following, start/stop contacts, or any other signal wires. Also, do not bundle motor

wires from multiple drives in the same conduit. Use shielded cables on all signal wiring over 12” (30 cm).

The shield should be earth grounded on the drive side only. Connect the drive in accordance with the

National Electrical Code requirements and other local codes that may apply.

Be sure to properly fuse each AC line conductor that is not at ground potential. Do not fuse neutral or

grounded conductors. A separate AC line switch or contactor must be installed as a disconnect so that

each ungrounded conductor is opened. For fuse or circuit breaker rating, see Table 3, on page 9. Also see

Section 6.1, below and on page 15.

The drive is designed with a removable cover. To open the cover, the two front cover screws must be

removed. After mounting and connections, install and tighten the two front cover screws to

5 in-lbs (6 kg-cm). Do not overtighten.

6.1

AC LINE INPUT CONNECTION – Connect the single-phase AC line input to Terminal Block TB1 (Terminals

“L1”, “L2”), as shown in Figure 7, on page 15.

The rated AC line voltage of the drive must match the actual AC line input voltage setting of Jumper

J1. The drive is factory set for 208/230 Volt AC line input (Jumper J1 not installed). For 115 Volt AC

line input, install Jumper J1 (supplied). See Section 7.1, on page 16.

14

Terminal Block

Description

Maximum Wire Size (Cu)

Recommended Tightening Torque

AWG

mm

2

in-lbs

kg-cm

TB1

AC Line Input and Motor Wiring

12

3.3

7

8

TB2

Run/Fault Relay Output Contacts

16

1.3

3.5

3

TABLE 4 – TERMINAL BLOCK WIRE & TIGHTENING TORQUE SPECIFICATIONS