GFCI Operation – Do not connect this

drive to an AC power source controlled by

a Ground-Fault Circuit-Interrupter. Special

software is available for GFCI operation –

contact our Sales Department.

AC Line Fusing – The drive does not contain

line fuses. Most electrical codes require that

each ungrounded conductor contain circuit

protection. Do not fuse neutral or ground

connections. It is recommended to install a

fuse (Littelfuse 326, Buss ABC, or equivalent)

or a circuit breaker in series with each

ungrounded conductor. Connect the drive in

accordance with the National Electrical Code

requirements and other local codes that may

apply to the application. Do not fuse motor

leads. For the recommended fuse size, see

Table 3, on page 9.

6.2

GROUND CONNECTION – Connect the ground (earth) wires from the AC line and motor to Terminal Block

TB1 (Terminal “GND”). See Figure 7.

6.3

MOTOR CONNECTION – Connect the motor to Terminal Block TB1 Terminals “U”, “V”, “W”. See Figure 7.

Motor cable length should not exceed 100 ft (30 m) – special reactors may be required – consult our Sales

Department. Be sure Jumper J2 is set to the corresponding motor horsepower rating, as described in

Section 7.2, on page 16.

Note: If the motor rotates in the incorrect direction, it will be necessary to disconnect the AC line and

change the position of the jumper on CON2 from “F” to “R” or reverse any two motor leads.

6.4

RUN/FAULT RELAY CONNECTION – The Run/Fault

Relay Output Contacts are located at TB2 and can be

used to turn on or off equipment or to signal a warning if a

fault has occurred or the drive is put into the Stop Mode*.

See Figure 8. The Run/Fault Relay Contact status for

various drive operating conditions is shown in Table 5, on

page 16. Also see Section 7.5, on page 18.

Relay Contacts Ratings – 1 Amp at 30 Volts DC, 0.5

Amps at 125 Volts AC, and 0.25 Amps at 250

Volts AC.

*In order for the Run/Fault Relay to give “Stop Mode” indication, the optional Forward-Stop Reverse Switch

(Part No. 9519) must be installed.

15

FIGURE 7 – AC LINE INPUT, MOTOR & GROUND CONNECTIONS

115* or 208/230 Volt

Single-Phase AC Line Input

3-Phase, 208/230 Volt

AC Induction Motor

AC LINE

MOTOR

Motor

TB1

U

V

Ground (Earth)

GND

W

L1

L2

* For 115 VAC line, install Jumper J1 (supplied).

FIGURE 8 – RUN/FAULT RELAY

OUTPUT CONTACTS CONNECTIONS

Normally Open

Normally Closed

Relay Common

Run/Fault Relay

Output Contacts

TB2

COM

N.C.

N.O.