The CL Trimpot is factory set to 160% of the drive rated current. To

increase the current limit, rotate the CL Trimpot clockwise. To decrease

the current limit, rotate the CL Trimpot counterclockwise. See Figure 22.

Figure 23 shows the I

2

t Trip Time vs. Motor Overload. Also see Section

4.2, on page 13.

*UL approved as an electronic overload protector for motors.

CAUTION! Adjusting the current limit above 160% of the motor

nameplate rating can cause overheating of the motor. Consult the motor

manufacturer. Do not leave the motor in a locked rotor condition for more than a few seconds since

damage may occur.

In order to ensure that the motor is properly protected with the I

2

t feature, it is required that the

CL Trimpot be set for 160% of the motor nameplate rated current, as described on page 16.

Note: This adjustment must be made within 6 seconds or an I

2

t Trip will occur.

The current limit may be adjusted as follows:

1.

Connect an AC RMS ammeter in series with one motor phase.

2.

Set the CL Trimpot fully counterclockwise.

3.

Adjust the speed setting to 30%.

4.

Lock the motor shaft and adjust the CL Trimpot to 160% of the motor nameplate rated current.

23

CL

120

80

40

160

200

FIGURE 22 – CURRENT LIMIT

TRIMPOT RANGE

(Shown Factory Set to 160% Full Load)

Tr

ip

Time (Minutes)

CL (Factory Setting)

140

110

120

130

0.1

Motor Current (%)

1

160

150

10

100

1000

FIGURE 23 – I

2

t TRIP TIME

VS

. MOTOR CURRENT