See Figure 1. Also see Section 4 – Important Application Information, on page 13.

WARNING! Disconnect main power before making connections to the drive.

Note: It is recommended that both Feed-Through Bushings be used to connect the drive. If signal wiring (for the

Run/Fault Relay Output Contacts or for a remote Main Speed Potentiometer) is required, it is recommended that

the extra Feed-Through Bushing (supplied with the drive) be used to replace the center Hole Plug. Standard 3/4”

fittings (not supplied) can also be used in lieu of the Feed-Through Bushings.

1.1

MOUNTING INSTRUCTIONS – See Section

5, on page 14.

1.2

AC LINE INPUT CONNECTION – Connect

the single-phase AC line input to Terminal

Block TB1 (Terminals “L1”, “L2”), as shown

in Figure 1. See Section 6.1, on pages 14

and 15.

Application Note – Do not connect this

drive to a GFCI. If operation with a GFCI

is required, contact our Sales Department.

Note: The drive is factory set for 208/230

Volt AC line input (Jumper J1 not installed).

For 115 Volt AC line input, install Jumper

J1 (supplied). See Section 7.1, on page 16.

1.3

AC LINE FUSING – It is recommended that a

fuse(s) or circuit breaker be installed in the AC line. Fuse each conductor that is not at ground potential.

For the recommended fuse size, see Table 3, on page 9. Also see Section 6.1, on pages 14 and 15.

1.4

GROUND CONNECTION – Connect the ground wire (earth) to Terminal Block TB1 (Terminal “GND”),

as shown in Figure 1, above.

1.5

MOTOR CONNECTION – Connect the motor to Terminal Block TB1 (Terminals “U”, “V”, “W”), as shown in

Figure 1, on page 4. (Special reactors may be required for cable lengths over 100 ft. (30 m) – consult our

Sales Department.). See Section 6.3, on page 15.

4

1

QUICK-START INSTRUCTIONS

Important – You must read these simplified instructions before proceeding. These instructions are to be used

as a reference only and are not intended to replace the details provided herein. You must read the Safety

Warning, on page 5, before proceeding.

Note: This drive contains bus capacitors which must be reconditioned if the drive has been in storage for over

1 year. To recondition the bus capacitors, apply the AC line, with the main speed potentiometer set to zero, for

a minimum of 30 minutes.

FIGURE 1 – QUICK-START CONNECTION DIAGRAM

115* or 208/230 Volt

Single-Phase AC Line Input

see Section 6.1, on pages 14 and 15.

* For 115 VAC line, install Jumper J1 (supplied).

3-Phase, 208/230 Volt

AC Induction Motor

see Section 6.3, on page 15.

AC LINE

MOTOR

Motor

TB1

U

V

Ground (Earth)

see Section 6.2,

on page 15.

GND

W

L1

L2