Installation

SPEEDMASTER™ OPERATION MANUAL

Power input

Connect the AC line power leads to PCB terminals L1 and L2, or
to a single-throw, double-pole master power switch
(recommended). The switch should be rated at a minimum of
250 volts and 200% of motor current.

Line fuse

Wire an external line fuse between the stop switch (if installed)
and the L1 terminal on the PCB. An additional line fuse should
be installed on L2 if the input voltage is 230VAC. The line
fuse(s) should be rated at 250 volts and 150 - 200% of
maximum motor nameplate current. Refer to the line fuse chart
on page 14 for fuse ratings.

See Table 2 for field output connections. Use 18 AWG wire to
connect the field output to a shunt wound motor.

Table 2. Field Output Connections

Line Voltage

Approximate Connect Motor

(VAC)

Field Voltage (VDC) Field To

115

50

F1 and L1

115

100

F1 and F2

230

100

F1 and L1

230

200

F1 and F2

Warning

The field output is for shunt wound motors only. Do not
make any connections to F1 and F2 when using a
permanent magnet motor.