Operation, Before applying power, Warning – LEESON SCR Thyristor Motor Control User Manual

Page 31: Figure 14. voltage switches, Speedmaster™ operation manual

Advertising
background image

25

SPEEDMASTER™ OPERATION MANUAL

Before applying power

• Set voltage switch SW501 to either 115 or 230 to match the

AC line voltage. Set voltage switch SW502 to either 90 or 180
to match the maximum armature voltage (see Figure 14).

• Verify that no conductive material is present on the printed

circuit board.

• If using a 90 VDC or 130 VDC motor with 230 VAC line

voltage, derate the nameplate motor speed and torque by at
least 30%.

IC502

S1

C502

IC501

A1

-

METER

+

SO502

SW501

115

230

MOV503

T501

L2

CL

IL501

SW502

90

180

C504

SO501

INHIBIT

S2

S3

+

-

SPEEDMASTER

L2

S2

S3

A1

S1

VOLTAGE

SWITCHES

Figure 14. Voltage Switches

Warning

Change voltage switch settings only when the drive is
disconnected from AC line voltage. Make sure both
switches are set to their correct position. If the switches are
improperly set to a lower voltage position, the motor will not
run at full voltage. If the switches are improperly set to a
higher voltage position, the motor will overspeed, which
may cause motor damage.