Symptom possible causes suggested solutions – LEESON SCR Thyristor Motor Control User Manual

Page 58

Advertising
background image

52

Troubleshooting

SPEEDMASTER™ OPERATION MANUAL

Symptom

Possible

Causes

Suggested

Solutions

Line fuse does not
blow or circuit breaker
does not trip, but the
motor does not run
(cont.)

Motor runs too fast at
maximum speed
setting

Motor runs too slow or
too fast

Motor will not reach
the desired speed.

3. Drive is in current limit.

4. Drive is not receiving

AC line voltage.

5. Motor is not connected.

1. MIN SPD and MAX

SPD settings are too
high.

MIN SPD and MAX SPD
are not calibrated.

1. MAX SPD setting is too

low.

2. IR COMP setting is too

low.

3. Motor is overloaded.

3. Verify that the motor is

not jammed. Increase
TORQUE setting (page
39).

4. Apply AC line voltage

to L1 and L2.

5. Connect motor to A1

and A2.

1. Recalibrate MIN SPD

(page 37) and MAX
SPD (page 38).

1. Recalibrate MIN SPD

(page 37) and MAX
SPD (page 38).

1. Increase MAX SPD

setting (page 38).

2. Increase IR COMP

setting (page 38).

3. Check motor load.

Resize the motor or
drive if necessary.