Appendix A: Ramp Soak

Copying the Setup from Another Profile

Use this menu to setup similar profiles quickly, by copying a profile to
another one.

Selectable Values: A to Q.

Editing the tolerance Alarm Time

Use this menu to set a tolerance time that applies to the entire profile.

When the segment goes out of tolerance,

•

The segment goes into tolerance hold

•

The segment timer holds

•

The loop’s single loop display shows TOHO (Tolerance Hold)

When the segment has been out of tolerance for more than the tolerance
alarm time,

•

The controller goes into tolerance alarm

•

The tolerance timer resets

You must acknowledge the tolerance alarm by pressing the ALARM
ACK key before you can do any other editing.

Selectable Values: 0:00 to 99:59 (minutes or hours, depending on the
time base setting).

LOOP PROCESS UNITS

ALARM SETPOINT STATUS OUT%

COPY SETUP
FROM PROFILE? A

LOOP PROCESS UNITS

ALARM SETPOINT STATUS OUT%

A OUT-OF-TOLRNCE
ALARM TIME? 1:00