40 CLS User’s Guide

Installation

You can connect J, K, T, S, R, B, and E thermocouples directly to the
CLS. Watlow Anafaze provides standard linearization and cold junction
compensation for these thermocouple types. (Other thermocouple types
require custom linearization; please contact Watlow Anafaze for more
information about them.)

Connecting Thermocouples

Connect the positive T/C lead to the In+ terminal. Connect the negative
T/C lead to the TB1 In- (4 or 8CLS) or analog common 16CLS)(
terminal. A typical thermocouple connection is shown in the figure
below.

•

Use 20 gauge thermocouple extension wire for all thermocouple

inputs.

•

If you use shielded wire, tie it to panel ground or to ground at the

measurement end.

RTD Inputs (4 and 8 CLS only)

The standard industrial RTD is an 100-ohm, 3-wire platinum assembly
as shown in the figure below. Watlow Anafaze highly recommends that
you use the 3-wire RTD to prevent reading errors due to cable
resistance.

•

If you order an RTD1 or RTD2 configuration, Watlow Anafaze will

configure your CLS for the standard 3-wire RTD.

•

If you must use a 4-wire RTD, leave the fourth wire unconnected.

Watlow Anafaze offers 2 standard DIN 385 curve RTD input ranges, as
shown here:

RTD Ranges in Degrees

Name

Temp. Range
in ºF

Temp.
Range in

º

C

Resolution

Measurement
Temperature

Error @ 25

º

C Ambient

Error @ 0-50

º

C Ambient

RTD1

-148.0 to
527.0 ºF

-100.0 to
275.0

º

C

0.023

º

C

25

º

C

±0.35 ºC

±0.5 ºC

275

º

C

±

1 ºC

±1.5 ºC

RTD2

-184 to 1544
ºF

-120 to 840

º

C

0.062

º

C

25

º

C

±0.9 ºC

±2.8 ºC

840

º

C

±1.1 ºC

±4.3 ºC

White

Red

Type J T/C

IN +

IN

–

Case

Shield (if present)

Frame Ground