background image

<2. Handling Cautions>

2-5

IM 01C25T04-01EN

Note 6. Installation Instructions

Non-Hazardous Location

Hazardous Location

F0202.ai

Terminator

Safety Barrier

Transmitter

Pressure

Transmitter

Transmitter

+

+

+

Terminator

+

+

[Installation Diagram]

SUPPLY

• In the rating 1(*1), the output current of the

barrier must be limited by a resistor ‘Ra’ such

that Io = Uo/Ra.

• In the rating 2(*2), the output of the barrier

must be the characteristics of the trapezoid

or the rectangle and this transmitter can be

connected to Fieldbus equipment which are

in according to the FISCO model.

• The terminators may be built in by a barrier.

• More than one transmitter may be connected

to the power supply line.

• The terminator and the safety barrier shall be

certified.

Electrical data:

Maximum Input Voltage Ui: 24 V

Maximum Input Current Ii: 250 mA

Maximum Input Power Pi: 1.2 W

Maximum Internal Capacitance Ci: 3.52 nF

Maximum Internal Inductance Li: 0 μH

*1:

Rating 1

or

Maximum Input Voltage Ui: 17.5 V

Maximum Input Current Ii: 380 mA

Maximum Input Power Pi: 5.32 W

Maximum Internal Capacitance Ci: 3.52 nF

Maximum Internal Inductance Li: 0 μH

or

Maximum Input Voltage Ui: 17.5 V

Maximum Input Current Ii: 460 mA

Maximum Input Power Pi: 5.32 W

Maximum Internal Capacitance Ci: 3.52 nF

Maximum Internal Inductance Li: 0 μH

*2:

Rating 2

c. ATEX Intrinsically Safe Ex ic
Caution for ATEX Intrinsically safe Ex ic

The transmitters with option code /KN26 for

potentially explosive atmospheres:

• Applicable Standard:

EN 60079-0:2009/EN 60079-0:2012,

EN 60079-11:2012

• Type of Protection and Marking Code:

II 3G Ex ic IIC T4 Gc

• Ambient Temperature: –30* to +60°C

* –15°C when /HE is specified.

• Maximum Process Temperature: 120°C

• Ambient Humidity:

0 to 100% (No condensation)

• IP Code: IP66

• Ambient pollution degree: 2

• Overvoltage category: I

Note 1. Electrical Data

Ui = 32 V

Ci = 3.52 nF

Li = 0 µH

Note 2. Installation

• All wiring shall comply with local installation

requirements. (refer to the control drawing)

• When installing the transmitter in “ic”

FISCO system or FNICO system, follow the

installation requirements of each system.

• Cable glands, adapters and/or blanking

elements shall be of Ex “n”, Ex “e” or Ex “d”

and shall be installed so as to maintain the

specified degree of protection (IP Code) of

the transmitters.

Note 3. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void ATEX

intrinsically safe.

Associated

Apparatus

Transmitter

Nonhazardous Area

[Control drawing]

Hazardous Area

+

F0203.ai

• Above drawing shows the installation of

Entity system.

When installing the transmitters in “ic”

FISCO system or FNICO system, follow the

installation requirements of each system.