<8. Diagnostic Information>

8-2

IM 01C25T04-01EN

Table 8.1

Contents of Condensed DIAGNOSIS

Octet Bit

DIAGNOSIS

Mnemonic

Description

Remarks

NAMUR

NE107

Category

1

0-7

Reserved

*2

Reserved for use within the PNO

---

---

2

0-3

Reserved

*2

Reserved for use within the PNO

---

---

3

DIA_WARMSTART

*1

New start-up (warm startup) carried out.

Should be set after power-on or after

FACTORY_RESET = 2506 has been

executed.

---

4

DIA_COLDSTART

*1

Restart (cold startup) carried out.

Should be set after FACTORY_RESET = 1

has been executed.

---

5

DIA_

MAINTENANCE

*2

Maintenance required

---

M

6

reserved

*2

---

---

7

IDENT_NUMBER_

VIOLATION

*2

Set to 1 (one), if the Ident_Number of the

running cyclic data transfer and the value

of Physical Block IDENT_NUMBER_

SELECTOR parameter do not correspond.

If IDENT_NUMBER_SELECTOR = 127

(adaption mode) then the DIAGNOSIS bit

IDENT_NUMBER_VIOLATION is cleared

/ not set.

---

C

3

0

DIA_

MAINTENANCE_

ALARM

Failure of the device or armature

Pressure Sensor Failure (AL.01)

Capsule Temp Sensor Failure (AL.01)

Capsule EEPROM Failure (AL.01)

AMP EEPROM Failure (AL.02)

AMP Temp Sensor Failure (AL.02)

CPU Board Failure 1 (AL.02)

CPU Board Failure 3,4 (AL.02)

CPU Board Failure 5 (AL.02)

F

1

DIA_

MAINTENANCE_

DEMANDED

*2

Maintenance demanded

---

M

2

DIA_FUNCTION_

CHECK

Device is in function check mode or in

simulation or under local control e.g.

maintenance

Diff Pressure Span /Zero Trim Error (AL.50)

Static Pressure Span/Zero Trim Error (AL.51)

STB Configuration Error (AL.60)

TOT in Man Mode (AL.72)

FB Simulation Active (AL.72, 90, 91, 92, 93,

94, 95 )

STB Simulation Active (AL.96)

PB Simulation Active (AL.97)

C

3

DIA_INV_PRO_

COND

The process conditions do not allow to

return valid values. (Set if a value has the

quality Uncertain - Process related, no

maintenance or Bad - Process related, no

maintenance

Diff Pressure Outside Range Limit (AL.10)

Static Pressure Outside Range Limit (AL.11)

Capsule Temp Outside Range Limit (AL.12)

AMP Temp Outside Range Limit (AL.13)

S

4-7

Reserved

*2

Reserved for use within the PNO

---

---

4

0-6

Reserved

*2

Reserved for use within the PNO

---

---

7

EXTENSION_

AVAILABLE

0: There is no more information available

1: More diagnosis information is available in

DIAGNOSIS_EXTENSION

---

---

*1: The indication will be automatically restart after 10 s.

*2: Not available for EJX and EJA-E series.