<9. Parameter Lists>

9-2

IM 01C25T04-01EN

Relative

Index

Index

Parameter

Write

Mode

Initial Value

Explanation

22

38

DEVICE_INSTAL_

DATE

AUTO

Date of installation of the device.

23

39

LOCAL_OP_ENA

AUTO

1: Enabled

Local operation enable.

0: Disabled

1: Enabled

24

40

IDENT_NUMBER_

SELECTOR

AUTO

127: Adaptation

Mode

The parameter to select Ident number.

0:Profile specific (Transmitter 3 AI)

1:Manufacturer specific (Ident number of DEVICE_ID)

127: Adaptation Mode

128: Profile specific 2 (Transmitter 1 AI)

129: Profile specific 3 (Transmitter 12 AI)

130: Profile specific 4 (Transmitter 1 AI+TOT)

131: Profile specific 5 (Transmitter 2 AI+TOT)

132: Profile specific 6 (Transmitter 3 AI+TOT)

140: Manufacturer specific (If EJA, Ident number of EJX)

25

41

HW_WRITE_

PROTECTION

0

Indicates the position of a write blocking mechanism which

can not be modified by remote access which protects

parameter modification of a device.

0:Unprotected

2:Protected

26

42

FEATURE

Indicates optional feature implemented in the device and

the status of these features which indicates if the feature is

supported or not supported.

27

43

COND_STATUS_

DIAG

AUTO

Condensed Status

and Diagnosis

information is

provided

Indicates the mode of a device that can be configured for

stats and diagnostic behavior.

0: Status and Diagnosis

1: Condensed Status and Diagnosis information is

provided

33

49

SOFT_DESC

“2.40 - 4581 - 1.01” Yokogawa internal use only

34

50

SET_ADDRESS

AUTO

0

For Bus address set up

35

51

SIM_ENABLE_MSG

AUTO

Software switch for simulation function

36

52

DEVICE_STATUS_1

AUTO

0x00000000

Device status

37

53

DEVICE_STATUS_2

AUTO

0x00000000

Device status

38

54

DEVICE_STATUS_3

AUTO

0x00000000

Device status

39

55

DEVICE_STATUS_4

AUTO

0x00000000

Device status

40

56

DEVICE_STATUS_5

AUTO

0x00000000

Device status

41

57

DEVICE_STATUS_6

AUTO

0x00000000

Device status

42

58

DEVICE_STATUS_7

AUTO

0x00000000

Device status

43

59

DEVICE_STATUS_8

AUTO

0x00000000

Device status

44

60

DIAGNOSIS_SIM_

MODE

AUTO

0: Disabled

For testing alarms and warnings can be modified. Switch to

enable or disable alarm simulation. When this parameter is

set to enable and the hardware simulation jumper is on, all

of alarms and warnings in DIAGNOSIS_EXTENSION can

be modified with DIAGNOSIS_SIM_EXTENSION.

0: Disabled

1: Enabled

45

61

DIAGNOSIS_SIM_

EXTENSION

AUTO

0x00, 0x00, 0x00,

0x00

For testing alarms and warnings can be modified. When

the hardware simulation jumper is on, DIAGNOSIS_SIM_

MODE is set to enable, and the bits are set to “on”, the

arlarms (or warnings) can be modified. (0x000000000000)

46

62

DIAGNOSIS_MASK_

EXTENSION_RW

AUTO

0xff, 0x3c, 0x33,

0xf0, 0x00, 0x00

Set masked DIAGNOSIS_EXTENSION.

When DIAGNOSIS_MASK_EXTENSION_RW-bit is

ON and its alarm or warning occurs, its DIAGNOSIS_

EXTENSION-bit is ON.

47

63

SI_CONTROL_

CODES

0

A parameter for switching to make the instrument

compatible with SI units.

48

64

IDENT_NUMBER

Ident number of the device

64

80

PRIVATE_1

Not used for the transmitter

65

81

PRIVATE_2

Not used for the transmitter

66

82

PRIVATE_3

Not used for the transmitter

67

83

PRIVATE_4

Not used for the transmitter

68

84

PRIVATE_5

Not used for the transmitter

69

85

PRIVATE_6

Not used for the transmitter

70

86

PRIVATE_7

Not used for the transmitter

71

87

PRIVATE_8

Not used for the transmitter

Advertising