<5. Parameter Setting>

5-12

IM 01C25T04-01EN

a. Display Selection

A cycle of up to four displays can be shown by

assigning variables to the parameters at

Display

Selection.

• Procedure to call up the display

DTM, EDD

Local Display → Display Selections →

Display Selection

b. Parameter Selection

At

Parameter Selection, select the variable that

will display on the integral indicator.

• Procedure to call up the display

DTM, EDD

Local Display → Display (1-4) Selections

→ Parameter Selection (1-4)

→ Display1

“on” or “off”

→ Display2

“on” or “off”

→ Display3

“on” or “off”

→ Display4

“on” or “off”

Set Parameter Selection 2, Parameter Selection

3 and Parameter Selection 4 in the same way if

necessary.
In addition to the above item, “Not used” is also

displayed as a selection item.

c. Information Selection

Information Selection parameter specifies

whether Display tag, Parameter, Unit or Status

should be displayed on bottom part of integral

indicator.

• Procedure to call up the display

DTM, EDD

Local Display → Display Selections

→ Information Selection

→ TAG

“on” or “off”

→ PARAMETER “on” or “off”
→ UNIT

“on” or “off”

→ STATUS

“on” or “off”

d. Display Tag

At

Display Tag parameter, user can set display tag

of up to 6 alphanumeric characters, slash (/) and

period (.).

• Procedure to call up the display

DTM, EDD

Local Display → Display (1-4) Setup →

Display Tag (1-4)

e. Unit Selection

Select whether unit to be displayed in the lower

text field should be automatically selected or

customized by user in parameter

Unit Selection.

Select “Auto” if you want to have unit chosen from

specified units and “Custom” for engineering unit

which you can input freely.

• Procedure to call up the display

DTM, EDD

Local Display → Display (1-4) Setup →

Unit Selection (1-4)

→ Auto

Select unit from the list

→ Custom

Input engineering unit by user

f. Display Unit

Display Unit parameter allows the engineering unit

to be displayed. Up to 6 alphanumeric characters

and one slash (/) and one period (.) can be input at

Display Unit; only the first six are displayed on the

integral indicator.

• Procedure to call up the display

DTM, EDD

Local Display → Display (1-4) Setup →

Display Unit (1-4)

Note that following symbols are not available.

# % & < > * : + - , ‘ ( )

The integral indicator shows “------“ when these

symbols or more than two slashes are entered.

g. Exponent Mode

User can change the position of decimal point

which is shown on the integral indicator. Select from

0, 1, 2, 3 or 4.

• Procedure to call up the display

DTM, EDD

Local Display → Display (1-4) Setup →

Exponent Mode (1-4)

Example of exponent setting:
The LCD value for exponent setting when the actual

pressure value is 23.4568kPa and the decimal point

is selected ‘2’.

Corresponding

decimal point

Exponent

LCD value

(kPa)

2

Engineering Unit

23.46

2

Eng. Unit@1/10

2.35

2

Eng. Unit@1/100

0.23

2

Eng. Unit@1/1000

0.02