<9. Parameter Lists>

9-5

IM 01C25T04-01EN

Relative

Index

Index

Parameter

Write

Mode

Initial Value

Explanation

71

87

STATIC_PRESSURE_

LOW_VALUE

72

88

SP_VALUE_TYPE

O/S

109: absolute

pressure

Select the type of measurement for static pressure,

absolute or gauge

73

89

SP_VALUE_URL

25000

Upper limit of static pressure value

74

90

SP_VALUE_LRL

0

Lower limit of static pressure value

75

91

CAL_SP_POINT_HI

O/S

25000

The highest calibrated value for static pressure

76

92

CAL_SP_POINT_LO

O/S

0

The lowest calibrated value for static pressure

77

93

CAL_SP_MIN_SPAN

500

The minimum calibrated span allowed for static pressure

78

94

CAL_SP_

DEVIATION_HI

O/S

0

Deviation value for zero adjustment of static pressure

79

95

CAL_SP_

DEVIATION_LO

O/S

0

Deviation value for span adjustment of static pressure

80

96

SP_VALUE_FTIME

O/S

2

Damping time constant for static pressure

81

97

ATM_PRESS

O/S

101.325

Atmoshpere pressure value used to obtain gauge pressure

value from absolute pressure

82

98

CLEAR_CAL

O/S

0

Reset zero and span adjustment to factory calibrated

values for pressure, static pressure and or all

83

99

TEMPERATURE_

VALUE_URL

130

Upper limit of temperature value

84

100

TEMPERATURE_

VALUE_LRL

-50

Lower limit of temperature value

85

101

AMP_TEMP_VAL

Value of amplifier temperature

86

102

AMP_TEMP_URL

95

Upper limit of amplifier temperature value

87

103

AMP_TEMP_LRL

-50

Lower limit of amplifier temperature value

88

104

CALCULATE_VALUE —

Calculation result of (Primary Value) × (Calculate

Coefficient)

89

105

CALCULATE_UNIT

O/S

1347 (m3/s)

Unit of CALCULATE_VALUE

90

106

CALCULATE_COEF

O/S

1

Coefficient for calculating Calculate Value (CALCULATE_

VALUE). Calculate Coefficient can be considered as

K-factor for flow rate calculation.

91

107

MODEL

Space

The model code

92

108

SPECIAL_ORDER_ID —

Space

Identification number of special order

93

109

MANUFAC_DATE

O/S

0, 0, 0, 0, 0, 0

Date of production

94

110

D_VENT_PLUG

O/S

Unknown

material of drain or vent plug

95

111

REM_SEAL_ISOL_

MTL

O/S

Unknown

Material of isolating diaphragm for remote seal

96

112

FLANGE_SIZE

O/S

Unknown

Flange size for remote seal

97

113

REM_SEAL_NUM

O/S

Unknown

Number of remote seal

98

114

REM_SEAL_FILL_

FLUID

O/S

Unknown

Type of fill fluid in remote seal

99

115

REM_SEAL_TYPE

O/S

Unknown

Type of remote seal

100

116

AUTO_RECOVERY

O/S

1 (ON)

Permission of auto recovery from sensor errors

101

117

MS_CODE

AUTO

Model suffix and code

102

118

SIMULATE_MODE

AUTO

0

Mode of simulation

103

119

SIMULATE_VALUE

AUTO

Value written by an operator to simulate Transducer Block

value

141

157

CURVE_X

AUTO

Parameter for signal charactrization

142

158

CURVE_Y

AUTO

Parameter for signal charactrization

158

174

TEST_KEY1

Not used for the transmitter

159

175

TEST_KEY2

Not used for the transmitter

160

176

TEST_KEY3

Not used for the transmitter

161

177

TEST_1

Not used for the transmitter

162

178

TEST_2

Not used for the transmitter

163

179

TEST_3

Not used for the transmitter

164

180

TEST_4

Not used for the transmitter

165

181

TEST_5

Not used for the transmitter

173

189

TEST_13

Not used for the transmitter

174

190

TEST_14

Not used for the transmitter

175

191

TEST_15

Not used for the transmitter