<4. Getting Started>

4-1

IM 01C25T04-01EN

4. Getting Started

PROFIBUS PA is fully dependent upon digital

communication protocol and differs in operation

from conventional 4 to 20 mA transmission.

HMI

Class 1 Master

I/O CARD, PLC, etc.

PROFIBUS-DP

PROFIBUS-DP devices

PROFIBUS-PA devices (DPharp)

PROFIBUS-PA (31.25 kbps)

Class 2 Master

FieldMate (FDT/DTM)

PDM (EDD), etc.

DP/PA

Coupler

F0401.ai

Figure 4.1

Profibus System Construction

4.1 Connection of Devices

The following are required for use with PROFIBUS

PA devices:

• Power supply:
PROFIBUS PA requires a dedicated power supply.

It is recommended that current capacity be well

over the total value of the maximum current

consumed by all devices.

Power is supplied by a DP/PA coupler.
• Terminators:
PROFIBUS PA requires two terminators.

A terminator shall be located at each end of the

trunk cable.
• Field devices:
Connect the PROFIBUS PA communication type

field device. Two or more transmitters or other field

devices can be connected.

• DP/PA Couplers:
PROFIBUS PA requires DP/PA couplers which

convert the RS-485 signals to the IEC 61158-2

signal level and power the field devices via the

PROFIBUS PA.
• Cable:
Refer to Table 4.1.

Table 4.1

PROFIBUS PA Cables and

Transmissible Length

Type of cable

Cable

specifications

Max. length

of cable

(reference

value)

Type A: Individually-

shielded twisted pair

cable

#18AWG

(0.82 mm

2

)

1,900 m

Type B: Overall-

shielded twisted pair

cable

#22AWG

(0.32 mm

2

)

1,200 m

Type C: Unshielded

twisted pair cable

#26AWG

(0.13 mm

2

)

400 m

Type D: Overall-

shielded non-twisted

cable

#16AWG

(1.25 mm

2

)

200 m

Note: Yokogawa recommends the use of Type A.

Usage of Type B and D is restricted.

Yokogawa does not recommend the use of Type C.

SUPPLY

CHECK

or

ALARM

+


+

Power supply and output terminal

Not used for PROFIBUS Communication type

Ground terminal

Communication

terminals

connection hook

*1: Not available for PROFIBUS communication type.

Check meter

connection hook

*1

SUPPLY +

SUPPLY –

CHECK – or ALARM –

*1

CHECK + or

ALARM +

*1

+

F0402.ai

Figure 4.2 Wiring Diagram