4 master settings, Master settings -3 – Yokogawa EJX115A User Manual

Page 19

Advertising
background image

<4. Getting Started>

4-3

IM 01C25T04-01EN

(3) Ident Number
Refer to section 4.5 for explanation of Ident

Number.
(a) Confirmation by the name plate

Device specific Ident Number and Profile Ident

number is marked on the name plate. Profile

Ident Number is inside [ ]. (9700 to 02(9720),

9740 to 42(9742))

Refer to Figure 4.3.

(b) Confirmation from integral indicator (When the

integral indicator code “E”)

Please refer to section 4.2.

(c) Confirmation by parameter

Ident Number can be confirmed from Physical

Block parameter Ident Number (IDENT_

NUMBER).

• Procedure to call up the display

DTM

Physical Block → Identification → ID No.

EDD

Identification → Device → ID No.

F0404.ai

SW: X.XX [ X . . . X ]

Device Revision

Device Revision Compatibility

Software Revision

ID: XXXX [ 9700-02, 9740-42 ]

Profile Ident Number

Device Specific Ident Number

(EJX: 4581 EJA: 4580)

Figure 4.3

Name Plate

4.4 Master Settings

To activate PROFIBUS PA, the following bus

parameters must be set for the master.

Table 4.2

Bus Parameters

Symbol

Parameter

Description and

Settings

Transmission

rate

Transmission

Rate

The transmission rate of

PROFIBUS PA matches

that of the segment

coupler.

e.g P+F: 93.75 kbps,

Siemens: 45.45 kbps

T

SL

Slot Time

The maximum time a

master station must

wait for the complete

reception of the first

octet of a response (11

bits).

e.g: 4095

min T

SDR

Min. Station

Delay Timer

Sets the minimum time

at which a slave can

send the first bit of a

response back.

max T

SDR

Max. Station

Delay Time

Sets the maximum time

at which a slave can

send the first bit of a

response back.

T

QUI

Quiet Time

Controls the time at

which the bus electronics

or software of the sender

is set to receive mode

after a message is sent.

T

SET

Setup Time

Sets the maximum

allowable time for

parameter setting and

response by the slave.

HSA

Highest

Station

Address

Sets the highest station

address in the network.

G

Gap update

factor

Sets the number of

token cycles after which

the master will search for

a new master.

max. retry

limit

Max Retry

Limit

Sets the number

of retries that are

performed after a

receiver does not

respond to a message.