<4. Getting Started>

4-4

IM 01C25T04-01EN

4.5 Integration of GSD file and

IDENT Number

The GSD file and Ident number are necessary

for PROFIBUS communication. Before starting

communication, the device must be specified by the

GSD file in the host system and the Ident number of

the device.
The PROFIBUS device has a profile Ident number

and a device-specific Ident number. There are GSD

files which correspond to each number. The profile

GSD file is a general-purpose file which is defined

by the kind and number of function blocks of the

device. This file helps improve the compatibility

among devices.
By setting the PROFIBUS Ident Number (IDENT_

NUMBER_SELECTOR) parameter of the physical

block or the Ident number at the Local Operation

Interface, the Ident number will be linked with the

corresponding GSD file. For the setting at the Local

Operation Interface, see Chapter 7.5.

Table 4.3

Device specific ID GSD file

Model Name

Device specific

Ident Number

Device Specific

GSD file

EJXA

0x4581

YEC4581.gsd

EJAE

0x4580

YEC4580.gsd

Table 4.4

Profile ID GSD file

Profile ID

Profile Ident

Number

Profile GSD file

AI ×1

0x9700

pa139700.gsd

AI ×2

0x9701

pa139701.gsd

AI ×3

0x9702

pa139702.gsd

AI ×1+TOT

0x9740

pa139740.gsd

AI ×2+TOT

0x9741

pa139741.gsd

AI ×3+TOT

0x9742

pa139742.gsd

4.6 Bus Address Setup

This section describes the procedure to set

Bus Address in the transmitter. Every device in

PROFIBUS must be assigned a unique address

in the range of 0(0x00) to 126(0x7e). If it is not

specified at the time of order, 126(0x7e) is the

factory default. Do not change to 0, 1 or 2 as these

are used by master devices.

There are two ways to set Bus Address: by using

communication tools or by Local Operation

Interface. Refer to chapter 7.5 for setting procedure

by using Local Operation Interface. Below is an

example of changing Bus Address from 5 to 20 by

using DTM works.

1. In the FieldMate window, click [Segment

Viewer] → [User Defined Connection] and click

[New FDT Project ...].

2. In the DTM Works window, click [Topology] →

[Add].

3. In the Catalog window, click [PROFIBUS DPV1]

of Protocol → [PROFIdtm DPV1] and click

[Add] button.

4. In the DTM Works window, click [Device] →

[Connect].

5. In the DTM Works window, click [Device] →

[Additional Functions] → [Set Device Station

Address...].

6. Enter [Old Address] to 5 and [New Address] to

20 and click [Set] button.

“New address successfully set” is displayed in

the State field.

7. Click [Close] button and exit DTM works
8. When changing a parameter after changing

the Address, click [View] → [Update] in the

FieldMate window.