<5. Parameter Setting>

5-1

IM 01C25T04-01EN

5. Parameter Setting

5.1 Easy Setup

IMPORTANT

After setting and sending data with the

configuration tool, wait 30 seconds before

turning off the transmitter. If it is turned off

too soon, the setting will not be stored in the

transmitter.

5.1.1 Tag Number, Descriptor, Message

and Installation Date

If there are specified when ordering, the desired Tag

No. is set and shipped. Tag No. can be checked as

follow.

• Procedure to call up the display

DTM, EDD

Easy Setup → TAG

When Tag No. is changed, input them based on the

following limitation.

Item

Limitations

TAG

Up to 32 characters or numbers

Descriptor

Up to 32 characters or numbers

Message

Up to 32 characters or numbers

Installation Date

Up to 16 characters or numbers

Sensor Calibration

Date

Manufacture Date

yyyy/mm/dd/ hh:mm:ss

- yyyy: years (4 digits)

- mm: month (2 digits)

- dd: days (2 digits)

- hh: hours (2 digits)

- mm: minutes (2 digits)

- ss: seconds (2 digits)

SP

!

"

#

$

%

&

'

(

)

*

+

,

-

.

/

0

1

2

3

4

5

6

7

8

9

:

;

<

=

>

?

@

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

[

\

]

^

_

`

a

b

c

d

e

f

g

h

i

j

k

l

m

n

o

p

q

r

s

t

u

v

w

x

y

z

{

|

}

~

*: SP shows one-byte space

5.1.2 Pressure Range (Scale In) and

Pressure Unit

Sensor Transducer Block Target Mode need to be

changed to Out of Service (O/S) before changing

range values and pressure unit.

DTM, EDD

Easy Setup → Sensor Transducer Block

→ Target Mode

(1) Pressure Range (Scale In)
The range values are factory-set as specified by

the customer. To change the range, follow the steps

below.

• Procedure to call up the display

DTM

Easy Setup → Sensor Transducer Block

→ Scale In →

LRV

Scale In:Lower Value

URV

Scale In:Upper Value

EDD

Easy Setup → Sensor Transducer Block

→ Measuring Range – Scale In →

→ LRV

Lower Value

→ URV

Upper Value

(2) Pressure Unit
The unit parameter is set at the factory before

shipment if specified at the time of order. Follow the

procedure below to change the unit parameter.

• Procedure to call up the display

DTM

Easy Setup → Sensor Transducer Block

→ Pressure Unit

EDD

Easy Setup → Sensor Transducer Block

→ Measuring Range – Scale In →

Pressure Unit

Available pressure units are shown below.

µPa

mPa

Pa

hPa

kPa

MPa

GPa

mbar

bar

torr

atm

psi

gf/cm

2

kgf/cm

2

inH

2

O

inH

2

O (4 deg C)

inH

2

O (68 deg C)

mmH

2

O

mmH

2

O (4 deg C)

mmH

2

O (68 deg C)

ffH

2

O

ffH

2

O (4 deg C)

ffH

2

O (68 deg C)

inHg

inHg (0 deg C)

mmHg

mmHg (0 deg C)

µPaa

µPag

mPaa

mPag

Paa

Pag

hPaa

hPag

kPaa

kPag

MPaa

MPag

GPaa

GPag

psia

psig

gf/cm

2

a

gf/cm

2

g

kgf/cm

2

a

kgf/cm

2

g