<5. Parameter Setting>

5-5

IM 01C25T04-01EN

(4) Reset Adjustment to Factory Setting
The Clear Calibration method can reset the

adjustment to the initial calibrated values that were

set. The amount of the adjustment performed with

the external zero-adjustment screw is returned the

initial setting as well.

• Procedure to call up the display

DTM

Calibration →

EDD

[Menu] → Device → Sensor

Calibration → Clear Calibration

→ Clear Calibration

(Method)

Reset adjustment to factory setting

5.3 Input Signal Setup

5.3.1 Low Flow Cut Off

Low cut mode can be used to stabilize the output

signal near the zero point. Note that this function is

only available when Output Mode (Characterization

Type) is “Square root”.

(%)

50

50

(%)

Output

20

0

Input

F0502.ai

Example: Low cut at 20%

Figure 5.1

Low Flow Cut Off

Follow the procedure below to change the low

cut point. Sensor Transducer Block Target Mode

needs to be changed to Out of Service (O/S) before

changing low cut point.

DTM

Input → Target Mode

EDD

Input → Sensor Transducer Block →

Target Mode

• Procedure to call up the display

DTM, EDD

Input → Sensor Transducer Block →

Characterization → Low Flow Cut Off

The low cut point has hysteresis so that the output

around the point is behaved as below figure.

(Hysteresis for the cut point: 10% of the cut point)

<Example>

Low cut: 20.00%

F0503.ai

10%

Output

Input

Hysteresis fixed at 10%
of the cut point

20%

22%

5.3.2 Primary Value Scale (Scale Out) and

Primary Value Unit

Primary value is measured value available to the

function block. Sensor Transducer Block Target

Mode needs to be changed to Out of Service (O/S)

before changing primary value scale and primary

value unit.

DTM

Input → Target Mode

EDD

Input → Sensor Transducer Block →

Target Mode

(1) Output Scale (Scale Out)
To change the Output Scale, follow the steps below.

• Procedure to call up the display

DTM

Input → Sensor Transducer Block →

Primary Value →

→ LRV

Scale Out:Lower Value

→ URV

Scale Out:Upper Value

EDD

Input

Sensor Transducer Block

Measured Value – Primary Value

→ LRV

Lower Value

→ URV

Upper Value

(2) Primary Value Unit
Follow the procedure below to change the unit

parameter.

• Procedure to call up the display

DTM

Input → Sensor Transducer Block →

Primary Value → Primary Value Unit

EDD

Input → Sensor Transducer Block →

Measured Value – Primary Value → Unit