<5. Parameter Setting>

5-6

IM 01C25T04-01EN

5.3.3 Signal Characterizer

Below is the example of performing the signal

characterizer as shown in Figure 5.2. Target Mode

of Sensor Transducer Block need to be changed

to Out of Service (O/S) before setting linearization

table. In order to use signal characterizer,

“User defined (table)” must be chosen for

Characterization Type. Refer to subsection 5.1.3 for

changing Characterization Type.

40%

100%

0%

20%

100%

Y

X

F0504.ai

Figure 5.2

<1> Configuration of new linearization table can be

performed in “Query Device” in “Device” menu

in top section of tool window.

• Procedure to call up the display

DTM

[Device] → Configuration →

Characterization → Table

Coordinate →

EDD

[Device] → Characterization →

Linearization →

→ Operation Mode Select the transaction of the user

defined table

Table 5.1

Operation Mode

Code

Description

0

Not initialized.

1

New operation characteristic, first value.

3

Last value, end of transmission, check table, or

swap the old curve with the new curve.

4

Delete point of table.

5

Insert point defined.

6

Replace point of table.

Select “1: New operation characteristic, first value”

for new operation.

<2> Enter Lower and Upper Scale In / Out value.

Refer to subsection 5.1.2 and 5.3.2 for

procedure. For this case, scales should be

entered shown as below.
Scale In: Lower Value

0

Scale In: Upper Value

100

Scale out: Lower Value

0

Scale unt: Upper Calue

100

<3> Enter Coordinate No. and X, Y value

• Procedure to call up the display

DTM

[Device] → Configuration →

Characterization → Table

Coordinate →

EDD

[Device] → Characterization →

Linearization →

→ Coordinate No.

Number of coordinate

→ X Y value couple

- X

Input value of linearization table

→ X Y value couple

- Y

Output value of linearization table

X_

i

=(PrV–ScaleIn_L)/(ScaleIn_U–ScaleIn_L)

Y_

i

=X_

i

×{(ScaleOut_U–ScaleOut_L)+ScaleOut_L}

(i=1 to 31)
PrV: Pressure Value

ScaleIn_L: Scale In:Lower Value

ScaleIn_U: Scale In:Upper Value

ScaleOut_L: Scale Out:Lower Value

ScaleOut_U: Scale Out:Upper Value
For this case, Coordinate No. and X/ Y values

should be entered shown as below.
Coordinate No.: 1

X Y value couple – X : 0.0

X Y value couple – Y : 0.0
Coordinate No.: 2

X Y value couple – X : 0.4

X Y value couple – Y : 0.2
Coordinate No.: 3

X Y value couple – X : 1.0

X Y value couple – Y : 1.0

<4> To definite linearization table, select Code: 3 in

Operation Mode shown in procedure <1> and

update linearization table.