<5. Parameter Setting>

5-7

IM 01C25T04-01EN

<5> To confirm entered coordinate.

• Procedure to call up the display

DTM

[Device] → Configuration →

Characterization → Table Data

EDD

[Device] → Characterization →

Linearization Table

5.3.4 Calculate Coefficient (For flow rate

calculation)

Calculate Coefficient is constant mainly for

calculation of flow rate output signal. Follow

below procedure to set the Calculate Coefficient.

Sensor Transducer Block Target Mode needs to

be changed to Out of Service (O/S) before enters

Calculate Coefficient.

DTM

Input → Target Mode

EDD

Input → Sensor Transducer Block →

Target Mode

• Procedure to call up the display

DTM, EDD

Input → Sensor Transducer Block →

Calculated Value → Calculate Coefficient

There are two methods for the calculation of the

Calculate Coefficient (below Kfactor).
Method 1: Calculating the Kfactor by flow

parameters

Method 2: Calculating the Kfactor by means of the

flow condition

Method 1. Calculating the Kfactor by flow

parameters.

<1> Selection of the flow equation

Select the desired operational expression

according to the fluid type and the flow unit

category shown in Table 5.2.

<2> Confirming the unit

The unit to be used in this calculation is as

follows:

Differential pressure: Pa

Static Pressure: kPa abs

Temperature: K

The dimension of the pressure unit Pa are

M•L

-1

•S

-2

Where M: mass (Kg)

L: Length (m)

S: Time (second)

<3> Preparation of flow parameters for Kfactor

calculation

Each parameter must be expressed in the

following units.

d: m,

ρb and ρnorm: Kg/m

3

C, β, ε and K has no dimensions

<4> Calculation of the unit conversion coefficient Nc

The flow rate value does not change

automatically when a flow unit parameter is set

for the transmitter, and is always output as Kg/s

(mass flow). M

3

/s (volume flow), Nm

3

/s (Normal

volume flow.)

In order to obtain a value in your designated

unit, it is necessary to set Nc.

Nc is a conversion coefficient for the flow and

DP unit that is designated to be used.

<5> Selection of the Kfactor equation and

calculation Select the Kfactor expression

according to the unit category shown in Table

5.2.

Calculate the Kfactor using the parameters and

the expression.

<6> Enter Kfactor as shown in beginning of this

section.

IMPORTANT

If either the setting of flow unit or differential

pressure unit is changed, Kfactor and Nc must

be recalculated.

Table 5.2

Flow Operational Expression

T0501.ai

Flow unit Category

Kfactor

Flow

Normal · Standard

Volume Flow
Volume Flow

Mass Flow

Kfactor = /4×Nc×C/ 1–β

4

×ε×d

2

× 2×ρb

Kfactor = /4×Nc×C/ 1–β

4

×ε×d

2

× 2×ρb /ρnorm

Kfactor = /4×Nc×C/ 1–β

4

×ε×d

2

× 2/ρb

Qm, Qv or Qv_norm = Kfactor × ∆P