<5. Parameter Setting>

5-10

IM 01C25T04-01EN

5.4 Output Signal Setup

5.4.1 Fail Safe Mode

Fail Safe Mode defines the Output Value and

Status (Quality) when status of input signal to AI

function block or Totalizer function block is BAD.

This function is valid only when Actual Mode of

AI function block or Totalizer function block is in

“AUTO”

• Procedure to call up the display

(AI function block)

DTM

Output → Analog Input (1-3) → Fail Safe

Mode

EDD

Output → Function Block (1-3) – Analog

Input → Fail Safe Mode → Fail Safe

Mode

• Procedure to call up the display

(Totalizer function block)

DTM

Output → Totalizer → Fail Safe Mode

EDD

Output → Function Block 4 – Totalizer →

Fail Safe Mode

5.4.2 Channel

Channel is the parameter to select the signal which

is calculated in SENSOR Transducer Block. Target

Mode of each Function Block need to be changed

to Out of Service (O/S).

DTM

Output → Analog Input (1-3), Totalizer →

Target Mode

EDD

Output → Function Block (1-3) – Analog

Input, Function Block 4 - Totalizer →

Target Mode

• Procedure to call up the display

DTM

Output → Analog Input (1-3),

Totalizer → Channel →

EDD

Output → Function Block (1-3)

– Analog Input, Function Block 4 -

Totalizer → Channel →

→ Pressure Value

Row pressure value before

scaling

→ Primary Value

Differential pressure value

→ Calculated Value Calculated value
→ Static Pressure

(H)

Static pressure value of high

pressure side

→ Static Pressure

(L)

Static pressure value of low

pressure side

→ Capsule

Temperature

Capsule temperature value

→ Amplifier

Temperature

Amplifier temperature value

5.4.3 Totalizer

This section shows procedure to set Signal Totalizer

function. Refer to subsection 5.4.2 for Channel

setting of Totalizer Function Block. Follow below

procedure to set signal totalizer function.
<1> Set Totalizer Value Set

• Procedure to call up the display

DTM

Output → Totalizer → Totalizer

Value Set →

EDD

Output → Function Block 4 –

Totalizer → Totalizer Value →

→ Totalize

Normal operation of the totalizer

→ Reset

Assign value 0 to totalizer

→ Preset

Assign value of present value to

totalizer

<2> Set Mode

• Procedure to call up the display

DTM

Output → Totalizer → Mode →

EDD

Output → Function Block 4 –

Totalizer → Mode →

→ Pos. and neg.

value

True arithmetic integration of the

incoming rate values

→ Positive value

only

Totalization of positive incoming

rate value only

→ Negative value

only

Totalization of negative incoming

rate value only

→ Hold Count

Totalization stopped